Step 10 Installing The Drain Hose And Drain Pipe - Samsung AC TN4PKC Series Instruction Manual

Hide thumbs Also See for AC TN4PKC Series:
Table of Contents

Advertisement

Pipe size
Pipe
(mm)
Ø 6.35 to Ø9.52
Liquid
pipe
Ø 12.7 to Ø19.05
Ø 6.35
Ø 9.52
Gas pipe
Ø 12.70
Ø 15.88
Ø 19.05
• When installing insulation in the places and
conditions below, use the same insulation that is
used for high humidity conditions.
<Geological condition>
High humidity locations such as shorelines, hot springs,
lake or riversides, and ridges (when part of the building
is covered by earth and sand)
<Operation purpose condition>
Restaurant ceiling, sauna, swimming pool etc.
<Building construction condition>
Ceilings frequently exposed to moisture and cooling are
not covered. For example, pipes installed at a corridor
of a dormitory and studio or near an exit that opens and
closes frequently.
Places (where the pipes are installed) that are highly
humid due to a lack of ventilation.
Step 10 Installing the drain hose and
drain pipe
1 Push the supplied drain hose as far as possible over
the drain socket.
2 Tighten the metal clamp as shown in the picture.
Insulation type (heating/cooling)
Standard
(Less than 30 °C, 85 %)
EPDM, NBR (mm)
9t
13t
13t
19t
3 Wrap the supplied large sealing pad over the metal
clamp and drain hose to insulate and fix it with clamps.
4 Insulate the complete drain piping inside the building
(field supply).
If the drain hose cannot be sufficiently set on a slope,
fit the hose with drain raising piping (field supply).
5 Push the drain hose up to insulation when connecting
the drain hose to drain socket.
Drain hose
High humidity
(Over 30 °C, 85 %)
9t
13t
19t
25t
Drain socket
Metal clamp
Drain hose
Large seailng pad
PVC Tube Joint
+ VP25 (OD: 32 mm, ID: 25 mm)
Remarks
The internal
temperature is
higher than 120 °C.
Drain pipe
Be sure to bond the drain
hose and the main pipe.
Drain pipe
13