REVERSE LOCKOUT (Parameter P10)
Used to prevent reverse rotation when the motor is to be used only in the forward rotation.
Data setting
value
0
1
Note)
When the reverse rotation prohibit setting is made, reverse rotation will be impossible
in both the local and external modes.
STOP MODE SELECT (Parameter P11)
Used to select whether to ramp-to-stop or coast-to-stop when stopping the inverter.
Data setting
value
0
1
STOP FREQUENCY (Parameter P12)
Used to set the frequency which the inverter output stops when the inverter decelerate to a
stop.
Data setting range (Hz)
DC BRAKE TIME and DC BRAKE LEVEL (Parameter P13 and P14)
The DC brake can be applied when the inverter output frequency drops below the stop
frequency during ramp-to-stop or when switching between forward run and reverse run.
When used with jog operation, positioning control can be carried out.
[Parameter P13: The DC brake time is set.]
Data setting range (sec)
[Parameter P14: The DC brake level is set.]
Data setting range
41
Reverse rotation enabled (both forward/reverse rotation enabled)
Reverse rotation prohibited (only forward rotation enabled)
Details
The frequency is decelerated by the stop signal according to
Ramp-to-stop
the deceleration time, and then the motor stops.
Coast-to-stop
The inverter output is shut off immediately by the stop signal.
0.5 to 60 (set in 0.1Hz increments)
000•0.1 to 120 (The brakes are not applied when 000 is set.)
0 to 100 (Set in increments of 5. The braking force will
increase when a larger value is set.)
Details
Explanation of operation