Poor Cooling Troubleshooting - Tadiran Telecom ANL-100 Service Manual

Power sky split system and package units
Table of Contents

Advertisement

SKY

8.2 Poor Cooling Troubleshooting.

Symptom
Refrigerant flow
1
failure
Air circulation
2
failure.
Installation failure.
3
Probable Cause
5. Refrigerant gas shortage.
6. Excessive overcharging
of refrigerant.
7. Gas leakage.
8. Clogging of strainer or
capillary tube.
9. 4-Way valve is
defective.
10. Solenoid 4-Way valve is
defective.
11. Compressor is defective.
12. Service valves are not
fully open.
Air filter is clogged.
1. Location of the indoor or
the outdoor units is not
according to the
instructions.
2. Refrigerant tubes between
the units are not installed
according to the
instructions.
-
Corrective Action
5. Charge refrigerant gas.
6. Recharge gas.
7. Repair leakage.
8. Replace strainer.
9. Replace 4-Way valve.
10. Replace solenoid.
11. Replace compressor.
12. Open the valves full.
Clean air filter.
1. Relocate units.
2. Relocate or replace tubes.
40
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents