7.5 Installing the Outdoor Unit

• Make sure to leave sufficient space around the unit. See figure 6-4 for minimum required
distance between the unit and nearby walls.
• Install the unit in a location with convenient access for service and maintenance purposes.
• Protect the unit from any heat source such as direct sun rays.
• Prevent from any dust or strong wind installation sites.
• Position the unit in such a way to minimize motor noise which reaches the user and
neighbors.
• The unit must be installed at least 5 cm. above a solid surface.
• Make sure that the unit is level.
• Fasten the unit legs to the base. Place the rubber absorbtion cushions (supplied) under the
unit's legs to prevent vibrations.
• For models ANL-100 and AVL-100/120/140 hanging installation is allowed. Install only
on special platform or concrete slab.
• A drainage tube can be connected to the outdoor unit to remove condensation formed
during heating mode operation.
Model
ANL-100
AVL-100
AVL-120
AVL-140
a
c
Fig. 7-4
a mm
b mm
700
600
700
600
800
700
800
700
-
27
d
b
Distance
c mm
1000
1000
1000
1000
-
d mm
200
200
200
200