R-22 outdoor split-system heat pump 13 seer 1.5 to 5 tons

Advertisement

INSTALLATION MANUAL

R-22
OUTDOOR SPLIT-SYSTEM HEAT PUMP
THGD / YHJD / CHJD / LHJD
MODELS: 13 SEER -
1.5 TO 5 TONS
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
TXV INSTALLATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Installation with Required Clearances . . . . . . . . . . . . . . . . . . . 2
Tubing Hanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Outdoor Unit Control Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Single Stage PSC Furnaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
R-22 Saturated Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
TEST Input Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for a matching indoor coil plus 15 feet of field supplied
lines.
Matching indoor coils are available with a thermal expansion valve or
an orifice liquid feed sized for the most common usage. The orifice size
and/or refrigerant charge may need to be changed for some indoor-out-
door unit combinations, elevation differences, or total line lengths. Refer
to Application Data covering "General Piping Recommendations and
Refrigerant Line Length" (Part Number 036-61920-001).
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
/ GHGD
LIST OF SECTIONS
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
SYSTEM OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
LIST OF FIGURES
PSC Air Handler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
CFM Selection Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Heat Pump Flow Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Demand Defrost Control Module . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Defrost Operation Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Wiring Diagram - Single Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
LIST OF TABLES
X/L Output Categories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Defrost Initiate Curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service, or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer, or service agency.
This product must be installed in strict compliance with the
enclosed installation instructions and any applicable local, state,
and national codes including, but not limited to building, electrical,
and mechanical codes.
INSPECTION
As soon as a unit is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier's delivery receipt. A separate request for
inspection by the carrier's agent should be made in writing. See Local
Distributor for more information.
ISO 9001
Certified Quality
Management System
LISTED
359513-UIM-A-0408

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 13 SEER - THGD and is the answer not in the manual?

Questions and answers

Summary of Contents for Johnson Controls 13 SEER - THGD

  • Page 1: Table Of Contents

    INSTALLATION MANUAL R-22 OUTDOOR SPLIT-SYSTEM HEAT PUMP THGD / YHJD / CHJD / LHJD MODELS: 13 SEER - / GHGD ISO 9001 Certified Quality 1.5 TO 5 TONS Management System LISTED LIST OF SECTIONS GENERAL ..........1 EVACUATION .
  • Page 2: Unit Installation

    AROUND PERIMETER AIR HANDLER TERMINAL BLOCK NEC CLASS 2 WIRING TO INDOOR COIL NOTE: ALL OUTDOOR WIRING CONTROL MUST BE WEATHERPROOF. ACCESS SEAL OPENING(S) WITH PANEL PERMAGUM OR EQUIVALENT FIGURE 1: Typical Installation with Required Clearances Johnson Controls Unitary Products...
  • Page 3: Tubing Hanger

    The reusable service valves are pro- elevation differences. vided to evacuate and charge per this instruction. Serious service problems can be avoided by taking adequate precau- tions to assure an internally clean and dry system. Johnson Controls Unitary Products...
  • Page 4: Txv Installations

    Reinstall the liquid line to the top of the thermal expansion valve. Hand modify the liquid line to align with casing opening. Braze the liquid line to the evaporator liquid connection. Nitrogen should be flowing through the evaporator coil. Johnson Controls Unitary Products...
  • Page 5: Electrical Connections

    This unit must be grounded with a separate ground wire in accor- dance with the above codes. The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel. Johnson Controls Unitary Products...
  • Page 6: Typical Field Wiring (Air Handler / Electrical Heat) - (Single Phase)

    To install, refer to instructions packaged with the acces- sory and Figures 7-8. Prior to the installation of the dehumidification control, the jumper across the HUMIDISTAT terminals on the indoor variable speed air handler or furnace CFM selection board must be removed. Johnson Controls Unitary Products...
  • Page 7: Thermostat Chart - Single Stage Heat Pump

    Pump OFF Other Part Numbers: Part Numbers: Part Number: SAP = Legacy SAP = Legacy S1-2HU16700124 265901 = 031-09166 67297 = 031-01975 FIGURE 7: Thermostat Chart - Single Stage Heat Pump – Single Stage PSC Furnaces Johnson Controls Unitary Products...
  • Page 8: Thermostat Chart - Single Stage Heat Pump - Psc Air Handler

    W1 and W2 electric heat staging options. Part Numbers: Part Numbers: Part Number: SAP = Legacy SAP = Legacy S1-2HU16700124 159480 = 031-09156 67297 = 031-01975 FIGURE 8: Thermostat Chart - Single Stage Heat Pump – PSC Air Handler Johnson Controls Unitary Products...
  • Page 9: Evacuation

    See Figure 10 "Heat Pump Flow Diagram" to trace the flow of refriger- ant through the system. Check flare caps on service ports to be sure they are leak tight. DO NOT OVERTIGHTEN (between 40 and 60 inch - lbs. maximum). Johnson Controls Unitary Products...
  • Page 10: Saturated Properties

    The ASCD timer can be bypassed by connecting the TEST terminals for three seconds while the thermostat is calling for compressor opera- tion (Y input signal energized). W1/66 PRESSURE VALVE SWITCH FIGURE 11: Demand Defrost Control Module Johnson Controls Unitary Products...
  • Page 11: Test Input Functionality

    X/L terminal when the heat pump is operating in a defrost cycle that • De-energize the outdoor fan has been forced using the TEST inputs. • Energize the reversing valve • Energize the auxiliary heat output through the W1/66 terminal. • Begin the maximum defrost cycle length timer Johnson Controls Unitary Products...
  • Page 12: Defrost Operation Curves

    No call for defrost Time Defrost (6 hour) prevented Defrost prevented from starting INHIBIT CURVE REGION B REGION A No call for Defrost Call for Defrost Time Defrost (6 hour) allowed AMBIENT TEMPERATURE FIGURE 12: Defrost Operation Curves Johnson Controls Unitary Products...
  • Page 13: Instructing The Owner

    Cooling operation is the same as any conventional air conditioning unit. WHEN THE SYSTEM IS FUNCTIONING PROPERLY AND THE The outdoor fan should be running, with warm air being dis- OWNER HAS BEEN FULLY INSTRUCTED, SECURE THE charged from the top of the unit. OWNER’S APPROVAL. Johnson Controls Unitary Products...
  • Page 14: Wiring Diagram

    SECTION X: WIRING DIAGRAM FIGURE 13: Wiring Diagram - Single Phase Subject to change without notice. Printed in U.S.A. 359513-UIM-A-0408 Copyright © 2008 by Johnson Controls, Inc. All rights reserved. Supersedes: Nothing Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069...