Tranquility ® (TY) Series Table of Contents Model Nomenclature General Information Unit Physical Data Horizontal Installation Field Conversion of Air Discharge Horizontal Installation Vertical Installation Piping Installation Water-Loop Heat Pump Applications Ground-Loop Heat Pump Applications Ground-Loop and Ground Water Heat Pump Applications Ground-Water Heat Pump Applications Water Quality Standards...
Page 2
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Tr a n q u i l i t y 2 2 ( T Y ) S e r i e s ®...
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y 2 2 ( T Y ) S e r i e s ®...
Page 8
(e.g. louvered door). Therefore, fi lter rails are the industry coated air coils. standard and are included on ClimateMaster commercial heat pumps for the purposes of holding the fi lter only. For ducted return applications, the fi lter rail must be removed and replaced with a duct fl...
(e.g. louvered door). Therefore, fi lter rails are the industry Internally insulate return transition duct to reduce noise standard and are included on ClimateMaster commercial Rev.: 2/13 heat pumps for the purposes of holding the fi lter only. For ducted return applications, the fi lter rail must be removed and replaced with a duct fl...
Page 12
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Tr a n q u i l i t y 2 2 ( T Y ) S e r i e s ®...
Length (2 ft [0.6m] Length Standard) Optional pressure-rated hose assemblies designed specifi cally for use with ClimateMaster units are available. Similar hoses can be obtained from alternate suppliers. Supply and return hoses are fi tted with swivel-joint fi ttings at one end to prevent kinking during installation.
Hose kits are available from ClimateMaster in different treatment and fi ltering will be necessary. confi gurations for connection between the unit and the piping system.
20 mesh] size. The ClimateMaster Water Quality Table provides water quality requirements for ClimateMaster coaxial heat exchangers. The water should be evaluated by an Rev.: 5/6/2014 S independent testing facility comparing to this Table and when properties are outside of these requirements, an external secondary heat exchanger must be used to isolate the heat pump heat exchanger from the unsuitable water.
Figure 17 to change the setting to 10°F [-12.2°C] refrigerant temperature, a more suitable temperature when using an antifreeze solution. All ClimateMaster units operating with entering water temperatures below 60°F [15.6°C] must include the optional water/refrigerant circuit insulation package to prevent internal condensation.
Acc2 typical slow closing water control valve wiring for Taco Relay 500 series (ClimateMaster P/N AVM) and Taco SBV series valves. Slow closing valves take approximately 60 seconds to open (very little water will fl ow before 45 AO1 Gnd...
IOM and or unit wiring diagram. Practically back plate against the wall so that it appears level and any heat pump thermostat will work with ClimateMaster so the thermostat wires protrude through the middle units, provided it has the correct number of heating and cooling stages.
C L I M A T E M A S T E R W A T E R - S O U R C E H E A T P U M P S Tr a n q u i l i t y 2 2 ( T Y ) S e r i e s ®...
Page 35
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y 2 2 ( T Y ) S e r i e s ®...
Page 36
Thermostat Compatibility – Most heat pump and heat/ (kOhm) (kOhm) -17.8 85.34 131.0 2.99 cool thermostats can be used with the DXM2, as well as -17.5 84.00 132.8 2.88 ClimateMaster communicating thermostats (ATC32). -16.9 81.38 134.6 2.77 10.4 61.70 136.4 2.67 12.2 58.40 138.2 2.58...
Pressurize and check the system for leaks and repair as installation. appropriate. 4. Verify that all strainers are in place (ClimateMaster recommends a strainer with a #20 stainless steel wire mesh). Start the pumps, and systematically check each vent to ensure that all air is bled from the system.
If temperature is within 5. Two factors determine the operating limits range, proceed with the test. If temperature is of ClimateMaster heat pumps, (a) return air outside of the operating range, check refrigerant temperature, and (b) water temperature. When any pressures and compare to table 11.
Page 41
T H E S M A R T S O L U T I O N F O R E N E R G Y E F F I C I E N C Y Tr a n q u i l i t y 2 2 ( T Y ) S e r i e s ®...
97B0075N15 ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time for order may be changed without notice and may not be as described herein. Please contact ClimateMaster’s Customer Service Department at 1-405-745-6000 for specifi c information on the current design and specifi...