Central Control Address (Group Number) Setting - Toshiba Compliant Manager BMS-CM1280TLE Installation Manual

Compliant manager bms-cm1280tle
Table of Contents

Advertisement

Compliant Manager
7
CENTRAL CONTROL ADDRESS (GROUP
NUMBER) SETTING
• Central control addresses must be assigned to all air conditioners to be controlled.
• Under the control of the Compliant Manager, central control address equals group number.
For address setting when connecting a TCC-LINK adapter to the central control system, refer to this
manual and the TCC-LINK adapter installation manual.
<Preparations for central control address (group number) setting>
• Turn on the power of all air conditioners.
• This Compliant Manager or a standard wired remote controller is necessary for setting central control addresses.
• Terminate the operation of air conditioners, and then set central control addresses.
* To set central control addresses with the Compliant Manager, initial communication with all connected indoor
and outdoor units must have been completed. Therefore, wait at least 10 minutes after power-on, and then start
central control address setting.
NOTE
If the address setting is made before the initial communication is completed, an address is not assigned
to some units.
• Connect terminals U1 and U2 in the outdoor unit (Header unit) to the relay connector of terminals U3 and U4.
• Set SW30-2 on the interface P.C. board of the outdoor unit (Header unit) to ON only for one system, and to OFF
for others.
* The location of SW30 is shown in the wiring diagram supplied with the outdoor unit.
<Setting central control addresses (group numbers)>
Use "manual setting from wired remote controller," "manual setting," or "automatic setting" to set central control
addresses.
A Manual setting from wired remote controller
Set central control addresses (group numbers) from a standard wired remote controller.
* The following setting procedure is described based on button operations of the wired remote controller RBC-
AMT32E or RBC-AMT31E.
(1) Press the
(Note: Do not press the
(2) Press the
(3) Set central control addresses (group numbers) with the
• Group numbers used for the Compliant Manager are central control addresses (DN item 03).
• The effective address range is 1 to 64. However, there must be no duplicate address on the same line.
• An address value of 99 is used as an unset address.
(4) Press the
(5) Press the
* This setting procedure may vary depending on the wired remote controller model.
* Perform these steps while air conditioners are not working.
B Manual setting
Set central control addresses (group numbers) manually from the Compliant Manager.
(1) Press the
(CODE No. C1 flashes.)
(2) Check CODE No. C1, and then press the
(3) Select the line on which the unit exists and the zone and group in which addresses are to be registered with the
LINE button, ZONE
13-EN
button and
button simultaneously for at least 4 seconds.
button during setting.)
button to change the CODE No. 03.
button to fix the setting.
button to exit the address setting mode.
button and ZONE
button simultaneously for at least 4 seconds.
and
buttons, and GROUP
buttons.
button.
and
– 14 –
Installation Manual
buttons.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Compliant manager bms-cm1280ftle

Table of Contents