9
CHANGING RETURN-BACK TIME/
TEMPERATURE SETTINGS
Return-back time and return-back temperature (CODE No. settings) can be changed using the following
procedure.
NOTE
Do not change the data of CODE No. 0A and the following item codes to prevent the remote controller from
malfunctioning.
CODE
No.
01
Return-back Enable/Disable
02
Return-back 1 Time, Heating
03
Return-back 1 Time, Cooling
04
Return-back 1 Temp., Heating
05
Return-back 1 Temp., Cooling
06
Return-back 2 Time, Heating
07
Return-back 2 Time, Cooling
08
Return-back 2 Temp., Heating
09
Return-back 2 Temp., Cooling
Changing settings
The following shows an example of changing the time (factory setting) in the case of return-back 1 heating from 30
minutes to 45 minutes.
(1) Change the mode to the CODE No. setting change mode.
Press the
(
and CODE No. flash.)
(2) Set the data of the CODE No..
1. Change the CODE No. to "02" with the SET TEMP.
2. Change the set data to "045" with the GROUP
(
3. Press the
4. To continuously change other settings, repeat steps 1 to 3 above.
NOTE
At this time, the entered data of the selected CODE No. has not been saved yet.
(3) Determine the change.
Press the
* When the data has completely been written in the memory, the CODE No. setting change mode is exited.
17-EN
Item
,
, and ZONE
buttons simultaneously for at least 4 seconds.
and CODE No. are still flashing.)
button to determine the data.
button to write the updated data in the memory of the remote controller.
Factory setting
001 (Enabled)
000 (Disabled), 001 (Enabled)
030 (30 minutes)
1 to 60 minutes (in units of 1 minute)
030 (30 minutes)
1 to 60 minutes (in units of 1 minute)
018 (18°C)
18 to 29°C (in units of 1°C)
028 (28°C)
18 to 29°C (in units of 1°C)
030 (30 minutes)
1 to 60 minutes (in units of 1 minute)
030 (30 minutes)
1 to 60 minutes (in units of 1 minute)
018 (18°C)
18 to 29°C (in units of 1°C)
028 (28°C)
18 to 29°C (in units of 1°C)
or
or
button.
and CODE No. change to lighting.