<DIP-SW3>
<1> Always OFF
• Always set this bit to OFF.
<2> Synchronization of Setting Zone data
OFF: With transfer
ON: Without transfer
This bit specifies whether to perform synchronous communication of Setting Zone
data between Compliant Managers.
* When this bit is set to ON (without transfer), synchronous communication is not
performed, and when zone setting is made, the data is not reflected in other
Compliant Managers.
<3> Always OFF
• Always set this bit to OFF.
<4> Fire alarm input switching
• OFF: CLOSE: Fire alarm (OPEN: Normal)
COM-DI
DI3
(Normal)
• ON: OPEN: Fire alarm (CLOSE: Normal)
COM-DI
DI3
(Normal)
Factory setting: All OFF
COM-DI
DI3
(Fire alarm)
COM-DI
DI3
(Fire alarm)
– 13 –