6. Repeat steps 4 and 5 to install the hinges on the rear rail.
7. Attach the latch plate (item 8 in illustration on page 54) with two M-8 (20 mm)
screws (item 1 in illustration on page 54).
8. Repeat step 7 to attach the latch plate in the rear of the rack.
9. Attach the triangular braces (item 6 in illustration on page 54) in both the front and
rear of the rack.
10. Install the latch bolts (item 7 in illustration on page 54).
6
7

Determine Your Next Step

Use the following to determine your next step:
v If the rack is being attached to a concrete (non-raised) floor, proceed to "Attach the
Rack to a Concrete (Non-Raised) Floor" on page 55.
v If the rack is being attached to a raised floor, proceed to "Attaching the Rack to a
Short or Long Raised Floor" on page 59.
v If the rack is not being attached to the floor, proceed to "Step 3. Position and Level
the PrimaryRack" on page 10.
54