Outdoor Unit Control Panel Led Display - Panasonic R410A Service Manual

Mini vrf system
Table of Contents

Advertisement

2. Outdoor Unit Control Panel LED Display

LED
D042(1)
D043(2)
(Both ON)
(OFF)
(ON)
(Both OFF)
1
(Blinking alternately)
(Both blinking)
2
(Blinking alternately)
3
4
5
6
After the power is turned ON (and automatic address setting is not in progress), no communica-
tion with the indoor units in that system is possible.
After power is turned ON (and automatic address setting is not in progress), 1 or more indoor
units are confirmed in that system; however, the number of indoor units does not match the
number that was set.
Automatic address setting was completed successfully. (After the power is turned ON, the
number of detected indoor units connected to that system matches the number that was set,
and regular communications are occurring.)
Automatic address setting is in progress.
At time of automatic address setting, the number of indoor units did not match the number that
was set.
Alarm display
LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats.
M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm
N = Alarm No.
Example: LED 1 blinks 2 times, then LED 2 blinks 17 times. The cycle then repeats.
Alarm is "P17."
(
: ON
Display meaning
5 - 4
Mini VRF SYSTEM
Trouble Diagnosis
: Blinking
: OFF )

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents