4. Mini VRF Alarm Codes
E16 alarm
Alarm code
Alarm meaning
Alarm conditions
Probable cause
Check
Correction
Example
Notes
E20 alarm
Alarm code
Alarm meaning
Alarm conditions
Probable cause
1
Check
Correction
2
Example
Notes
Position of serial connector 1
CR-CHX06052
3
4
5
E25 alarm
Alarm code
Alarm meaning
6
Alarm conditions
Probable cause
Check
Correction
Example
Notes
E16
Automatic address setting alarm (too many units)
• The number of indoor units was too many when automatic address setting was performed.
• After initial communications were completed, an unrecognized unit was detected.
(1) The number of indoor unit setting SW (S004) on the outdoor unit PCB is too small.
(2) The inter-unit control wiring is wired incorrectly.
(1) Refer to the test run servicing materials and check the number of indoor units that is set.
(2) Check the inter-unit control wiring at the indoor and outdoor units.
After correcting the indoor unit quantity setting or the inter-unit control wiring, perform automatic
address setting again.
—
—
E20
No indoor units at automatic address setting.
When automatic address setting was performed, no indoor units were recognized.
(1) The inter-unit control wiring from the outdoor unit to the indoor units has been cut.
(2) Serial connector 1 (CN32) is disconnected at the outdoor unit.
(3) The power is OFF at all indoor units in the system.
(1) Check whether the inter-unit control wiring from the outdoor unit to the indoor units is cut.
(2) Check whether serial connector 1 (CN32) is disconnected at the outdoor unit.
(3) Check the power at the indoor units.
(1) Repair inter-unit control wiring from outdoor / indoor units.
(2) Plug connector 1 (CN32) in correctly.
(3) Turn on the power to indoor units.
—
E25
Outdoor unit address setting failure (duplication)
Communication by outdoor unit main-sub control wiring was received that contained the
same address as that unit 5 times or more within 3 minutes.
The unit number is set incorrectly.
Check the unit number again.
Correct the incorrect unit number setting.
—
Recovery from this alarm occurs automatically (when communication that contains the same
address is not received for 3 minutes).
5 - 8
Mini VRF SYSTEM
Trouble Diagnosis
CN32