Panasonic R410A Service Manual page 65

Mini vrf system
Table of Contents

Advertisement

2. Detailed Settings Function
Item code
Item
Automatic drain pump
operation
Ventilation fan operation
Wired remote controller
sensor
"Operation change
control in progress"
display
OFF reminder function
for when weekly timer is
used
Discharge temperature
control
Heat exchanger
temperature for cold air
discharge
(Heat exchanger control
point for control to
prevent cold air)
Fan output switching
Drain pump delayed
start time
Humidifi er setting
Flap operation mode
Flap swing mode
No.
0000
No forced operation
0001
Forced operation for 1 minute
0060
Continuous operation
0000
None
0001
Ventilation fan operated by remote controller.
0000
Not used. (Body sensor is used.)
0001
Remote control sensor is used.
0000
Normal (displayed)
0001
Not displayed
0000
None
0001
Only stop time setting is enabled.
0000
Discharge temperature control OFF
0001
Discharge temperature control ON
0013
Control temperature 55°F
0014
Control temperature 57°F
0025
Control temperature 77°F
0026
Control temperature 78°F
0000
Output linked with fan. (ON when indoor unit fan is operating.)
0001
Fan mode operation output
0000
No delayed start
0001
1 sec. delayed start
0002
2 sec. delayed start
0058
58 sec. delayed start
0059
59 sec. delayed start
0060
60 sec. delayed start
0000
Humidifi er output OFF. Drain pump stopped.
0001
Humidifi er output ON. Drain pump operates.
Humidifi er output ON. Drain pump operates for 1 minute when total humidifi er
0002
operating time reaches 60 minutes.
0003
Humidifi er output ON. Drain pump stopped.
0000
Standard setting
0001
Draft reduction mode (Flap lower-limit position is shifted upwards.)
0000
Smudging reduction mode (Flap swing upper-limit position is shifted downwards.)
0001
Normal mode
0002
Draft reduction mode (Flap swing lower-limit position is upwards.)
4 - 7
Mini VRF SYSTEM
Remote Controller Functions
Setting data
Description
1
2
3
4
5
6