4. Mini VRF Alarm Codes
P29 alarm
Alarm code
P29
Alarm meaning
Inverter compressor missing phase or lock alarm
Alarm conditions
This alarm may occur at start, and occurs when missing phase or lock is detected, and when a
DCCT failure occurs.
Probable cause
Generally this alarm occurs when the refrigerant pressure balance is uneven at start, when
inverter compressor lock occurs, there is a missing phase in the inverter compressor wiring, or a
DCCT failure occurs. This can be judged to be starting trouble which is not caused by HIC.
Check
Check the power wiring and connector wiring.
Correction
DCCT failure (replace PCB) or compressor failure
Example
Notes
Use a tester to measure the voltage between the DCCT output terminal on the rear of the PCB
and the ground. If the voltage is not within 2 – 3 V, then the DCCT has malfunctioned.
5 - 17