6. Mode Settings

■ Setting mode 1
<Operating procedure>
Press and hold the
(VENTILATION) button simultaneously for 4
seconds or longer.
Press the temperature setting
buttons to change the item code. The item codes
and setting data are shown in the table below.
Press the timer time
change the setting data.
To confirm the changed setting data, press the
button.
(At this time, "
lit.)
During this mode, "
The outdoor unit address display section displays
1
"ALL," the item code number (DN value in the
table), and the setting data (8 digits).
(The setting data is displayed in 8 digits. The
display changes between the first 4 digits (Fig.
2
and the last 4 digits (Fig.
digits are displayed, the bottom dot of the colon is
illuminated.)
To exit the setting mode, press the
button.
3
4
5
DN
Outdoor unit fan Quiet
mode
6
Energy saving mode
Energy saving operation
plug
Demand 1 current
Demand 2 current
(CHECK) button and
and
and
buttons to
" stops blinking and remains
" is displayed, blinking.
). When the first 4
B
(CHECK)
Parameter
0 = Disabled
1 = Quiet mode
0 = None
1 = Discharge temp. control only (Mode 3)
2 = Demand only (Mode 2)
3 = Discharge temp. control + Demand (Mode 1)
0 = Independent
1 = All indoor units linked
0 = 0% 1 = 40 ... 4 = 70 7 = 100 8 = 120
9 = 140 10 = 160 11 = 200 12 = –1 (no limit)
0 = 0% 1 = 40 ... 4 = 70 7 = 100 8 = 120
9 = 140 10 = 160 11 = 200 12 = –1 (no limit)
Outdoor Unit Maintenance Remote Controller
A
Display of fi rst 4 digits
5
1
B
Display of last 4 digits
A
)
5
1
B
and
are displayed alternately.
A
(Example shows display of 0000 0001.)
Description
3 - 12
Mini VRF SYSTEM
3
3
2
2