Outdoor Unit Alarm History Monitor - Panasonic R410A Service Manual

Mini vrf system
Table of Contents

Advertisement

5. Outdoor Unit Alarm History Monitor

Displays outdoor unit alarms only.
Check the indoor unit alarm histories separately using the
indoor unit remote controllers or other control device.
<Operating procedure>
Press and hold the
button simultaneously for 4 seconds or longer to engage
outdoor unit alarm history mode.
During temperature monitoring,
The display and operations are the same as for the
alarm history monitor performed from the indoor unit
remote controller. However the "unit No." display shows
the outdoor unit address.
Press the temperature setting
buttons and select the item code for the alarm history.
The select outdoor unit address, the item code, and the
alarm history (alarm data) are displayed.
The outdoor unit address is displayed as R.C. XX-YY.
System XX = Outdoor unit system address
R.C. XX = Outdoor unit system address
YY = Outdoor unit sub-bus address
Item codes 01-08 are displayed. 01 indicates the most
recent alarm.
The alarm history displays the alarm code. (If no alarm
are present, then -- -- is displayed.)
To clear the alarm history, press the
outdoor unit alarm history will be cleared.)
To exit, press the
(CHECK) button. The display
returns to the normal display.
(CHECK) button and
displays.
and
button. (The
Outdoor Unit Maintenance Remote Controller
1
4
3 - 11
Mini VRF SYSTEM
2
3
1
2
3
4
5
6