1. The stove must be placed on solid concrete,
solid masonry, or when installed on a com-
bustible floor, on a listed floor protector, use a
minimum 3/8" noncombustible floor protector
with an "R" factor of 0.8 such as Hy-C or Impe-
rial Model UL 4260BK or equivalent. (NOTE:
To calculate R-values of equivalent alternative
materials, see page 16). The base must extend
at least 16" beyond the side with the access
door, 8" to the sides, 15" to the backside of
stove and must extend under the stove pipe
if it is elbowed towards a wall. (See figures 3
& 4 and consult local building codes and fire
protection ordinances.)
CAUTION: (FIRE HAzARD) CARPETING AND
OTHER COmBUSTIBLE mATERIAL mUST NOT
COVER THE FLOOR PROTECTOR. THESE
mATERIALS mUST REmAIN OUTSIDE OF
COmBUSTIBLE CLEARANCES, SEE FIG. 3-5.
2. The stove must have its own flue. DO NOT
CONNECT ThIS uNIT TO a ChImNEy
fluE SErvINg OThEr aPPlIaNCES.
3. After observing the clearances to combustible
materials (figures 4 & 5), locate your floor
protector accordingly (figure 3) and care-
fully place the stove in your selected location.
Install stove pipe, elbows, and thimble as
required, utilizing either a recently cleaned
and inspected 6" masonry chimney or a 6"
i.d. listed chimney.
4. Use 6" round black stove pipe, not
galvanized stove pipe. Secure pipe sections
28"
SIDEWALL
Fig. 3 – TOp VIEw Minimum Clearance Dimensions from Combustible Surfaces
Page 4
/ VG810CL Sentry CoaL™
18"
DASHED LINE SHOWS STRAIGHT
OUT CHIMNEY CONNECTOR
AND ADDITIONAL FLOOR
PROTECTOR REQUIRED
8"
FLOOR PROTECTOR
14"
32"
with three (3) sheet metal screws in each stove
pipe and/or elbow joint to firmly hold the pipe
sections together. Do Not coNNect this stove
to aNy air DistributioN or Duct system.
5. R e c h e c k c l e a r a n c e s f r o m t h e s t ove ,
connector stove pipe, and corner clearances
using the illustrations in figures 3 – 5 and
your local building codes or fire protection
ordinances.
NOTE: A wall faced with drywall, brick
or stone must be considered a combustible
surface.
6. Do not install this stove in a mobile
home,trailer or tent – NO EXCEPTIONS!
(HUD Federal Standard: 24 CFR Ch.XX)
7. The clearances provided are minimum di-
mensions determined by the manufacturer's
testing facility. Installation of this stove must
comply with the latest edition of NFPA 211 for
reduced clearances and/or your local building
code rulings (use whichever minimum dimen-
sions are LARGEST).
Failure to follow these minimum clearance
requirements may result in an unsafe instal-
lation and could cause a fire.
8. This stove meets U.S. Test Standard:
UL 1482-1996.
CAUTION: KEEP FURNISHINGS AND OTHER
COmBUSTIBLE mATERIALS AwAY FROm THE
STOVE.
TOP VIEW
COMBUSTIBLE CONSTRUCTION IN
ACCORDANCE WITH NFPA 211
60"
16"
Continued on next page
BACKWALL
15"
42"
19"
8"
VGZ-011 / 20110513.1