During the warranty period, SOCOMEC UPS reserves the right to decide whether the product should be repaired, or whether to replace defective parts with new parts, or used parts that are equivalent to new parts in terms of functionality and performance.
Read the manual carefully before connecting the unit to the a.c. mains supply and to the downstream appliances. Before the UPS NETYS RT is put into commission, the user must be perfectly familiar with its operation, with the position of all the controls and with the technical and functional characteristics of the unit, so as to ensure there will be no risk to any persons or to the appliance itself.
1. SAFETY STANDARDS 1.2 DESCRIPTION OF THE SYMBOLS USED ON THE LABELS APPLIED TO THE UNIT All the precautions and the warnings on the labels and plates on the inside and outside of the equipment should be respected. DANGER! HIGH VOLTAGE (BLACK/YELLOW) GROUND TERMINAL READ THE USER MANUAL BEFORE USING THE UNIT 5-11 kVA - Ref.: IOMNETRTXX01-GB 05...
Consult the following check list when installing the UPS: • NETYS RT units are designed for use in enclosed environments. • Position the UPS on a flat and stable surface in a properly ventilated room, well away from heat sources and avoiding direct exposure to sunlight.
Page 11
2. INSTALLATION 2.4.3 Rotation of battery extension panel 5-11 kVA - Ref.: IOMNETRTXX01-GB 05...
Page 12
2. INSTALLATION 2.4.4 Fixing to rack 1. Adapt the length of the tracks to fit the rack. 2. Secure the wing nuts. 3. Fix the track to the rack. 4. Slot in the UPS and tighten the screws. MAX 100 kg MAX 100 kg MAX 100 kg MAX 100 kg...
3. REAR VIEW COM. SLOT PARALLEL RS232 RS232 PARALLEL 5 kVA 9 kVA 7 kVA 11 kVA Legend A EPO (Emergency Power Off) B Fan C Battery extension socket D Output terminals E Input terminals F Input switch G RJ45 LAN ethernet connector H Parallel D connector RS232 serial connector (JBUS protocol) L Slot for optional communication cards...
4. CONNECTIONS Connection to the mains power supply and to the load(s) must be made using cables of suitable cross section, in accordance with current standards. If not already provided, install a PDU panel allowing isolation of the mains supply upstream of the UPS. The panel must be equipped with an automatic switch rated high enough to handle the current draw on full load, and with a residual current device.
5. CONNECTION OF BATTERY EXTENSION 5.1 SAFETY WARNINGS • Before connecting the battery extension, check that it is fully compatible with the model of UPS in use. • The use of battery extensions not supplied by the manufacturer is inadvisable. WARNING! There is a risk of explosion if battery modules are replaced with others of incorrect type.
Page 17
5. CONNECTION OF BATTERY EXTENSION ON-OFF ON-OFF switch switch COM. SLOT PARALLEL RS232 RS232 PARALLEL 5 kVA 9 kVA 7 kVA 11 kVA Connection of multiple batteries COM. SLOT RS232 PARALLEL 5-11 kVA - Ref.: IOMNETRTXX01-GB 05...
6. CONNECTION OF BY-PASS AND SINGLE UPS 6.1 INSTALLATION OF BY-PASS AND SINGLE UPS TO CONNECT WITH WIRES:LOOSEN SCREWS MARKED BY 200-240Vac 200-240Vac 50/60Hz 50/60Hz TO UPS PARALLEL PORT TO UPS OUTPUT TO UPS INPUT AC OUTPUT AC INPUT MINI COM. SLOT INPUT BREAKER 230Vac...
6. CONNECTION OF BY-PASS AND SINGLE UPS 6.2 CONNECTION OF BY-PASS TO SINGLE UPS 6.2.1 Fixing the BY-PASS to the UPS Ensure parallel cable with DB9 connectors is installed between bypass switch and UPS. WARNING! Failure to install this cable will result in incorrect operation of the bypass function and damage to the UPS or connected equipment.
Page 20
6. CONNECTION OF BY-PASS AND SINGLE UPS 6.2.3 Connection of cables to the UPS terminal strips 5-11 kVA - Ref.: IOMNETRTXX01-GB 05...
Page 21
6. CONNECTION OF BY-PASS AND SINGLE UPS 6.2.4 Connection of cables to the BY-PASS terminal strips UPS output UPS input 5-11 kVA - Ref.: IOMNETRTXX01-GB 05...
Page 22
6. CONNECTION OF BY-PASS AND SINGLE UPS 6.2.5 Connection of cables to the BY-PASS input and output terminal strips UPS input UPS output UPS output UPS input 5-11 kVA - Ref.: IOMNETRTXX01-GB 05...
7. CONNECTION OF BY-PASS AND UPS IN PARALLEL 7.1 VERTICAL INSTALLATION OF BY-PASS AND UPS IN PARALLEL 7.1.1 Assembly of BY-PASS and UPS for vertical installation 7.1.2 Fixing BY-PASS to UPS for vertical installation Manual bypass is for 5/7/9/11 kVA models only. 5-11 kVA - Ref.: IOMNETRTXX01-GB 05...
7. CONNECTION OF BY-PASS AND UPS IN PARALLEL 7.2 RACK INSTALLATION OF BY-PASS AND UPS IN PARALLEL 7.2.1 Fixing brackets for rack installation 7.2.2 Fitting BY-PASS to rack 5-11 kVA - Ref.: IOMNETRTXX01-GB 05...
7. CONNECTION OF BY-PASS AND UPS IN PARALLEL 7.3 CONNECTION OF BY-PASS AND UPS IN PARALLEL 7.3.1 Connection of BY-PASS to 2 UPSs 7.3.1-1 7.3.1-2 output UPS 2 input UPS 2 7.3.1-3 7.3.1-4 output UPS 1 input UPS 1 5-11 kVA - Ref.: IOMNETRTXX01-GB 05...
Page 26
7. CONNECTION OF BY-PASS AND UPS IN PARALLEL 7.3.2 Connection of BY-PASS to line and load 7.3.2-1 7.3.2-2 LINE LOAD 7.3.2-3 5-11 kVA - Ref.: IOMNETRTXX01-GB 05...
7. CONNECTION OF BY-PASS AND UPS IN PARALLEL 7.4 CONNECTION OF BY-PASS TO UPS IN PARALLEL COM. SLOT COM. SLOT RS232 RS232 WARNING! NETYS RT models can only work with a maximum of 2 units in parallel. 5-11 kVA - Ref.: IOMNETRTXX01-GB 05...
8. MIMIC PANEL The mimic panel on the front of the UPS provides all essential information on the operating status of the appliance. Legend A Display. B Red symbol lit. Fault. C 2 colour LEDs: • Green - Normal. • Red - Overload. D Green LED lit.
9. OPERATING MODES 9.1 SWITCHING THE NETYS RT ON 9.1-1 9.1-2 9.1-3 3 sec short 9.1-4 9.2 SWITCHING THE NETYS RT OFF 9.2-1 9.2-2 short 3 sec 3 sec short 5-11 kVA - Ref.: IOMNETRTXX01-GB 05...
9. OPERATING MODES 9.4 OPERATION IN BY-PASS MODE FOR MAINTENANCE PURPOSES - SINGLE UPS COM. SLOT RS232 BY-PASS selector NORMAL - TEST - BYPASS ON-OFF switch Manual bypass is for 5/7/9/11 kVA models only. 5-11 kVA - Ref.: IOMNETRTXX01-GB 05...
Page 32
9. OPERATING MODES 9.4.1 Activation of by-pass mode for UPS maintenance purposes 9.4.1-1 9.4.1-2 9.4.1-3 • Wait 2 seconds before switching • UPS is by-passed but still to "BYPASS" switched on 9.4.1-4 9.4.1-5 9.4.1-6 • Switch-off also the Battery Cabinet. short •...
NETYS RT no-break systems are equipped with RS232 serial communication interface, and slots for NetVision cards. 10.1 COMMUNICATION SOLUTIONS •...
Page 35
10. COMMUNICATION 10.4.1 Internal circuit 10.4.1-1 10.4.1-2 Common R1 General alarm R2 No mains R3 Battery low R4 On by-pass R5 Overload R6 Overtemperature CPU Pin GND-R GND-R Input 10.4.1-3 GND-R Common Input GND-C 10.4.2 Standard confi guration relay contact GND-R: Relay ground contact Common: 12~24 V DC General alarm...
Page 36
10. COMMUNICATION 10.4.3 Customized confi guration for relay and/or input contacts Connect Tx to pin 2, Rx to pin 3 and GND-C to pin 5 of the computer’s RS232 port. In Windows, start the Hyper-Terminal application and proceed to open the specified COM port. Set the following properties: Baud rate: 2400, Data Bits: 8, Parity: None, Stop Bit: 1, Flow Control: None.
• Recharge the batteries for a duration of 24 hours at least every 4 weeks during the time the unit remains idle. 11.1 MINOR TROUBLESHOOTING WARNING! If problems should persist or reoccur frequently after following the procedures indicated in this section, contact the SOCOMEC UPS After Sales Service, providing a full description of the current difficulty Problem Possible cause Solution "UPS not powered up...
12. TECHNICAL SPECIFICATIONS Models NRT2-U5000 NRT2-U7000 NRT2-U9000 NRT2-U11000 UPS power 5000 VA 7000 VA 9000 VA 11000 VA 4500 W 5400 W 7200 W 9000 W Input 230 V (1 ph) ± 20% (up to -50% at 50% nominal load) Input socket Terminals Output...