12.8 Dry Mode

12.8.1
Dry, ST or RC group
Mode: Dry
Temp: Selected desired temp
Fan:
Low (automatically selected by software)
Timer: Any
I FEEL:
Any
Control function
Reduce room humidity with minimum temp. fluctuations by operating in Cool Mode with
low speed IFAN.
(RT - SPT) [
+2
+1
0
-1
-2
DRY-ON
DRY
DRY-OFF
LOW
IFAN
OFF
ON
COMP
OFF
& OFAN
ON
HE1
OFF
& HE2
ON
RV
OFF
Notes :
When Dry is ON, the COMP is forced OFF for 3.5 min (longer than the
3 min Min COMP-Off time) after every 15 min of continuous COMP
operation.
When Dry is OFF, the COMP is forced ON for 6 min (longer than the 3
min Min COMP-On time) after every 15 min of continuous COMP OFF
time.
When Dry is changed from ON to OFF or vice versa, the limits
mentioned in (1) & (2) are ignored. The COMP operation is only
controlled by the 3 min Min OFF time and 1 min Min ON time.
In Dry Mode, IFAN is LOW when COMP is ON, and is OFF when
COMP is OFF.