Indoor Fan Control in Heat Mode
Indoor fan speed depends on the indoor coil temperature:
11.5
Auto Cool/Heat Mode
When in auto cool heat mode unit will automatically select between cool and heat mode according
to the difference between actual room temperature and user set point temperature (ΔT).
Unit will switch from cool to heat when compressor is off for 3 minutes, and ΔT < -3.
Unit will switch from heat to cool when compressor is off for 5 minutes, and ΔT < -3.
11.6

Dry Mode

As long as room temperature is higher then the set point, indoor fan will work in low speed and
compressor will work between 0 and MaxNLOADIF1C Hz.
When the room temperature is lower than the set point, compressor will be switched OFF and
indoor fan will cycle 3 minutes OFF, 1 minute ON.
11.7
Protections
There are 5 protection codes.
Normal (Norm) – unit operate normally.
Stop Rise (SR) – compressor frequency can not be raised but does not have to be decreased.
HzDown1 (D1) – Compressor frequency is reduced by 2 to 5 Hz per minute.
HzDown2 (D2) – Compressor frequency is reduced by 5 to 10 Hz per minute.
Stop Compressor (SC) – Compressor is stopped.
11.7.1
Indoor Coil Defrost Protection
ICT
ICT < -2
-2 ≤ ICT < 0
0 ≤ ICT < 2
2 ≤ ICT < 4
4 ≤ ICT < 6
6 ≤ ICT < 8
8 ≤ ICT
SM DELTA 1-E.2 GB
ICTST
ICTVL
Fast
Increasing
Increasing
SC
SC
D1
D1
SR
SR
SR
SR
Norm
Norm
Norm
Norm
CONTENT
ICTL
ICTH
ICT Trend
No change
Decreasing
SC
SC
D2
D1
SR
SR
SR
Norm
SR
Normal
CONTROL SYSTEM
ICTT
Fast
Decreasing
SC
D2
D2
D2
D2
D1
D2
D1
SR
11-5