Dry Mode

As long as room temperature is higher then the set point, indoor fan will work in low speed and
compressor will work between 0 and MaxNLOADIF1C Hz.
When the room temperature is lower than the set point, compressor will be switched OFF and
indoor fan will cycle 3 minutes OFF, 1 minute ON.
11.7
Protections
There are 5 protection codes.
Normal (Norm) – unit operate normally.
Stop Rise (SR) – compressor frequency can not be raised but does not have to be decreased.
HzDown1 (D1) – Compressor frequency is reduced by Down1 Hz/min.
HzDown2 (D2) – Compressor frequency is reduced by Down2 Hz/min.
Stop Compressor (SC) – Compressor is stopped.
11.7.1
Indoor Coil Defrost Protection
ICT
ICT < -2
-2 ≤ ICT < 0
0 ≤ ICT < 2
2 ≤ ICT < 4
4 ≤ ICT < 6
6 ≤ ICT < 8
8 ≤ ICT
11.7.2
Indoor Coil over Heating Protection
ICT
ICT > 55
53 < ICT ≤ 55
49 < ICT ≤ 53
47 < ICT ≤ 49
45 < ICT ≤ 47
43 < ICT ≤ 45
ICT ≤ 43
SM DELTAZ 1-E.0 GB
Fast
Increasing
Increasing
SC
SC
D1
D1
SR
SR
SR
SR
Norm
Norm
Norm
Norm
Fast
Decreasing
Decreasing
SC
SC
D1
D1
SR
SR
SR
SR
Norm
Norm
Norm
Norm
CONTENTS
ICT Trend
No change
Decreasing
SC
SC
D2
D2
D1
D2
SR
D1
SR
SR
Norm
SR
Normal
ICT Trend
No Change
Increasing
SC
SC
D2
D2
D1
D2
SR
D1
SR
SR
Norm
SR
Normal
CONTROL SYSTEM
Fast
Decreasing
SC
D2
D2
D2
D1
SR
Fast
Increasing
SC
D2
D2
D2
D1
SR