Electra DELTA 22 Service Manual

Indoor/outdoor unit, r410a

Advertisement

DUO 38 DCI / DELTA
Indoor Units
Outdoor Units
DELTA 22
DUO 38 DCI
DELTA 25
DELTA 35
REFRIGERANT
R410A
HEAT PUMP
SEPTEMBER – 2008
SM DUO38 1-E.1 GB
CONTENT

Advertisement

Table of Contents
loading

Summary of Contents for Electra DELTA 22

  • Page 1 DUO 38 DCI / DELTA Indoor Units Outdoor Units DELTA 22 DUO 38 DCI DELTA 25 DELTA 35 REFRIGERANT R410A HEAT PUMP SEPTEMBER – 2008 SM DUO38 1-E.1 GB CONTENT...
  • Page 2 LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page (when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
  • Page 3 TABLE OF CONTENTS Table of Contents INTRODUCTION ....................1-1 PRODUCT DATA SHEET ..................2-1 RATING CONDITIONS ..................3-1 OUTLINE DIMENSIONS ..................4-1 PERFORMANCE DATA ..................5-1 PRESSURE CURVES ...................6-1 ELECTRICAL DATA ....................7-1 WIRING DIAGRAMS .....................8-1 REFRIGERATION DIAGRAMS ................9-1 10. TUBING CONNECTIONS ..................10-1 11. CONTROL SYSTEM .....................11-1 12.
  • Page 4: Introduction

    Each indoor unit is supplied with its own installation and operation manuals. Matching Table 1.5.1 R410A INDOOR UNITS OUTDOOR UNITS MODEL REFRIGERANT DELTA 22 DCI DELTA 25 DCI DELTA 35 DCI √ √ √ DUO 38 DCI R410A SM DUO38 1-E.1 GB...
  • Page 5: Product Data Sheet

    PRODUCT DATA SHEET PRODUCT DATA SHEET Outdoor Unit DUO 38 DCI / Delta Specifications. Model Indoor Unit DELTA 22 25 35 Model Outdoor Unit DCI DUO Delta 38 R410A Installation Method of Pipe Flared Characteristics Units Cooling Heating Btu/hr 13300(4090-18750)
  • Page 6 PRODUCT DATA SHEET Indoor Units Data 2.2.1 DELTA 22 DCI Specifications Model Indoor Unit / Type DELTA 22 DCI / Wall Mounted Installation Method FLARE Power Supply V/Ph/Hz 220-240 / 1/ 50 Fan Type & Quantity Crossflow *1 Airflow H/M/L...
  • Page 7: Product Data Sheet

    PRODUCT DATA SHEET 2.2.3 DELTA 35 DCI Specifications Model Indoor Unit / Type DELTA 35 DCI / Wall Mounted Installation Method FLARE Power Supply V/Ph/Hz 220-240 / 1/ 50 Fan Type & Quantity Crossflow *1 Airflow H/M/L Cooling / Heating Sound Power Level L - H dB (A)
  • Page 8: Rating Conditions

    RATING CONDITIONS RATING CONDITIONS Standard conditions in accordance with ISO 5151, ISO 13253 (for ducted units) and EN 14511. Cooling: Indoor: C DB 19 C WB Outdoor: 35 C DB Heating: Indoor: C DB Outdoor: 7 C DB 6 C WB Operating Limits Indoor Outdoor...
  • Page 9: Outline Dimensions

    OUTLINE DIMENSIONS OUTLINE DIMENSIONS Indoor Unit: DELTA 22, DELTA 25 DCI MOUNTING TEMPLATE TO BE USED FOR LOCATION CEILING OF INDOOR UNIT ON THE WALL INDOOR UNIT OUTLINE TUBING WALL OPENING (FOR REAR ROUTING) TUBING WALL OPENING (FOR REAR LEFT ROUTING)
  • Page 10 OUTLINE DIMENSIONS Outdoor Unit: DUO 38 DCI / Delta SM DUO38 1-E.1 GB CONTENT...
  • Page 11: Performance Data

    PERFORMANCE DATA PERFORMANCE DATA Delta 22+22 DCI 5.1.1 Cooling Capacity (kW) - Run Mode (Unit A or B) 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [0C] OD COIL ENTERING AIR 24/17 27/19 29/21 32/23...
  • Page 12 PERFORMANCE DATA 5.1.3 Heating Capacity (kW) - Run Mode(Unit A or B) 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [C OD COIL ENTERING AIR DB/WB TEMPERATURE DATA 1.15 1.07 1.00 -15/-16 0.38 0.44 0.49 1.37 1.30 1.23...
  • Page 13 PERFORMANCE DATA Delta 25+25 DCI 5.2.1 Cooling Capacity (kW) - Run Mode (Unit A or B) 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [0C] OD COIL ENTERING 24/17 27/19 29/21 32/23 AIRDB TEMPERATURE DATA 22/15 80 - 110 % of nominal 80 - 105 % of nominal...
  • Page 14 PERFORMANCE DATA 5.2.3 Heating Capacity (kW) - Run Mode(Unit A or B) 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ OD COIL ENTERING AIR DB/WB DATA TEMPERATURE [ 1.20 1.12 1.05 -15/-16 0.41 0.47 0.53 1.44 1.36...
  • Page 15 PERFORMANCE DATA Delta 25+35 5.3.1 Cooling Capacity (kW) - Run Mode(Unit A or B) 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB/WB TEMPERATURE [ OD COIL 24/17 27/19 29/21 32/23 ENTERING AIR DB DATA 22/15 TEMPERATURE [ 80 - 110 % of nominal -10 - 20 (protection 80 - 105 % of nominal...
  • Page 16 PERFORMANCE DATA 5.3.3 Heating Capacity (kW) - Run Mode(Unit A or B) 230[V] : Indoor Fan at High Speed. ID COIL ENTERING AIR DB TEMPERATURE [ OD COIL ENTERING AIR DB/WB DATA TEMPERATURE [ 1.73 1.62 1.52 -15/-16 0.59 0.67 0.76 2.07 1.97...
  • Page 17 PERFORMANCE DATA Capacity Correction Factor Due to Tubing Length (OneWay) 5.4.1 Delta 22 / 25 / 35 DCI 5.4.2 Cooling Capacity Ratio VS.Tubing Length - Cooling 1.02 1.00 0.98 0.96 0.94 0.92 0.90 0.88 Tubing Length [m] 5.4.3 Heating Capacity Ratio VS. Tubing Length - Heating 1.02...
  • Page 18: Pressure Curves

    PRESSURE CURVES PRESSURE CURVES Model: Delta 22+22, Delta 25+25 DUO 38 DCI 6.1.1 Cooling – Test Mode Suction Pressure VS.Outdoor Temp'. 1400 1300 Indoor DB/WB Temp'. 1200 1100 2 2 / 1 5 2 4 / 1 7 1000 2 7 / 1 9...
  • Page 19 PRESSURE CURVES 6.1.2 Heading – Test Mode Suction Pressure VS.Outdoor Temp'. 1100 1000 Indoor DB Temp'. Outdoor WB Temperature [ºC] Discharge Pressure VS. Outdoor Temp'. 3250 Indoor DB 3000 Temp'. 2750 2500 2250 2000 1750 1500 Outdoor WB Temperature [ºC] SM DUO38 1-E.1 GB CONTENT...
  • Page 20 PRESSURE CURVES Model: Delta 25+35 DUO 38 DCI 6.2.1 Cooling – Test Mode Suction Pressure VS.Outdoor Temp'. 1200 Indoor DB/WB 1100 Temp'. 1000 2 2 / 1 5 2 4 / 1 7 2 7 / 1 9 2 9 / 2 1 3 2 / 2 3 Outdoor DB Temperature [ºC] Discharge Pressure VS.
  • Page 21 PRESSURE CURVES 6.1.2 Heading – Test Mode Suction Pressure VS.Outdoor Temp'. 1100 1000 Indoor DB Temp'. Outdoor WB Temperature [ºC] Discharge Pressure VS. Outdoor Temp'. 3250 3000 Indoor DB Temp'. 2750 2500 2250 2000 1750 1500 Outdoor WB Temperature [ºC] SM DUO38 1-E.1 GB CONTENT...
  • Page 22: Electrical Data

    ELECTRICAL DATA ELECTRICAL DATA Power Supply 1 PH, 220-240 VAC, 50Hz Connected to Outdoor Maximum Current 13.7 A Inrush Current 35 A Starting Current 10 A Circuit breaker 16 A Power supply wiring - No. x cross section 3 X 2.5 mm Interconnecting cable - No.
  • Page 23: Wiring Diagrams

    WIRING DIAGRAMS WIRING DIAGRAMS DUO 38 DCI / DELTA Wiring Diagram EEV1 EEV2 SM DUO38 1-E.1 GB CONTENT...
  • Page 24: Refrigeration Diagrams

    REFRIGERATION DIAGRAMS REFRIGERATION DIAGRAMS Heat Pump Models 9.1.1 DUO 38 DCI => Cooling Mode SM DUO38 1-E.1 GB CONTENT...
  • Page 25 REFRIGERATION DIAGRAMS 9.1.2 DUO 38 DCI => Heating Mode SM DUO38 1-E.1 GB CONTENT...
  • Page 26: Tubing Connections

    TUBING CONNECTIONS TUBING CONNECTIONS TUBE (Inch) ¼” ⅜” ½” ⅝” ¾” TORQUE (Nm) Flare Nuts 11-13 40-45 60-65 70-75 80-85 Valve Cap 13-20 13-20 18-25 18-25 40-50 Service Port Cap 11-13 11-13 11-13 11-13 11-13 Valve Protection Cap-end Refrigerant Valve Port (use Allen wrench to open/close) Valve Protection Cap Refrigerant Valve Service Port Cap...
  • Page 27: Control System

    CONTROL SYSTEM CONTROL SYSTEM 11.1 General Functions and Operating Rules (for single split models) The DCI software is fully parametric. All the model dependent parameters are shown in Blue color and with Italic style [parameter]. The parameters values are given in the last section of this control logic chapter of the service manual.
  • Page 28 CONTROL SYSTEM 11.3.2 Target Frequency Setting The compressor target frequency is a function of the NLOAD number sent from the indoor controller and the outdoor air temperature. Basic Target Frequency Setting: NLOAD Target Frequency Maximum frequency 10 < NLOAD < 127 Interpolated value between minimum and maximum frequency Minimum frequency Compressor is stopped...
  • Page 29: Indoor Fan Control

    CONTROL SYSTEM 11.4 Indoor Fan Control 10 Indoor fan speeds are determined for each model. 5 speeds for cool/dry/fan modes and 5 speeds for heat mode. When user sets the indoor fan speed to a fixed speed (Low/ Medium/ High), unit will operate constantly at set speed.
  • Page 30: Fan Mode

    CONTROL SYSTEM 11.7 EEV (electronic Expansion valve) Control EEV opening is defined as EEV = EEV + EEV • is the initial EEV opening as a function of the compressor frequency, operation mode, unit model and capacity. • is a correction value for the EEV opening that is based on the compressor temperature.
  • Page 31: Heat Mode

    CONTROL SYSTEM 11.14 Heat Mode NLOAD is calculated according to the difference between actual room temperature and user set point temperature by PI control. In high/ medium/ low indoor fan user setting, unit will operate fan in selected speed. In AutoFan user setting, fan speed will be adjusted automatically according to the calculated NLOAD.
  • Page 32: Dry Mode

    CONTROL SYSTEM 11.16 Dry Mode As long as room temperature is higher then the set point, indoor fan will work in low speed and compressor will work between 0 and MaxNLOADIF1C Hz. When the room temperature is lower than the set point, compressor will be switched OFF and indoor fan will cycle 3 minutes OFF, 1 minute ON.
  • Page 33 CONTROL SYSTEM 11.17.3 Compressor over Heating Protection Compressor temperature can be in one of 5 control zones (4 in protection, and 1 normal), t. Stop-Compresor CTTOH4 CTTOH3 CTTOH2 CTTOH1 Normal Compressor Temperature Control Status Else Increases Norm Stop Compressor 11.17.4 Compressor over Current Protection Stop-Compresor CCROC4...
  • Page 34 CONTROL SYSTEM 11.17.5 Heat Sink Over Heating Protection (NA for DCI 25 and 35) HST Trend Decreasing No Change Increasing HST > 90 85 < HST ≤ 90 82 < HST ≤ 85 80 < HST ≤ 82 78 < HST ≤ 80 Norm Norm HST ≤...
  • Page 35 CONTROL SYSTEM 11.17.6.2 Deicing Protection Procedure Threshold COMP max. 12 minutes HEAT COOL OFAN EEVDeicerOpen T1 = T2 = 36 seconds, T3 = 6 seconds 11.17.7 Condensate Water Over Flow Protection Each of the pins P1, P2, P3 can have two options: 1 –...
  • Page 36 CONTROL SYSTEM Water Level LEVEL4 LEVEL2&3 LEVEL1 Pump NLOAD BLINK OPER LED NORMAL 11.17.7.2 1 Level Logic (used in all models except for floor/ceiling models) Level Don’t Normal care Don’t Overflow care Overflow when Overflow when unit is ON unit is OFF Overflow Water Level Normal...
  • Page 37 CONTROL SYSTEM 11.18 Indoor Unit Dry Contact Indoor unit Dry contact has two alternative functions that are selected by J8. Function Contact = Open Contact = Short J8 = Open Presence Detector Connection No Limit Forced to STBY J8 = Short Power Shedding Function No Limit Limit NLOAD...
  • Page 38 CONTROL SYSTEM 11.20.2 Indoor Unit Controls and Indicators for LCD Display STBY Cool Heat Auto SPT(1*) SPT(1*) SPT(1*) SPT(1*) SPT(1*) OFF(2*) ON(2*) ON(2*) ON(2*) ON(2*) ON(2*) OFF(2*) OFF(2*) OFF(2*) OFF(2*) OFF(2*) OFF(2*) (Low) (Med) User User User User User (High) setting setting setting...
  • Page 39: Jumper Settings

    CONTROL SYSTEM 11.21 Jumper Settings 11.21.1 Indoor Unit Controller 0 = Open Jumper (disconnect jumper). 1 = Close Jumper (connect jumper). Self test Jumper – J1 OPERATION SELF-TEST NORMAL Compensation Jumper – J2 Model J2 (Default) Compensation Wall Mounted Activated Floor/Ceiling Deactivated Ducted/cassette...
  • Page 40 CONTROL SYSTEM Model selection Jumper – J6, J7 Model 9000 Btu/hr 12000 Btu/hr 18000 Btu/hr 24000 Btu/hr J8- Clock/Power Shedding Operation Clock Power Shedding J9 – IFAN Cycling Disabling Display Mode (wall mounted units only) 11.21.2 Outdoor Unit Controller 11.21.2.1 JP9 JUMPER LAYOUT Reserved (PIN 9) ODU3 (PIN 7) ODU2 (PIN 5)
  • Page 41: Test Mode

    CONTROL SYSTEM 11.22 Test Mode 11.22.1 Entering Test Mode System can enter Test mode in two ways: • Automatically when the following conditions exists for 30 minutes continuously: o Mode = Cool, Set point = 16, Room temperature = 27±1, Outdoor temperature = 35±1 o Mode = Heat, Set point = 30, Room temperature = 20±1, Outdoor temperature = 7±1...
  • Page 42: Dry Contacts Control

    CONTROL SYSTEM 11.23.4 EEV (electronic Expansion valve) Control EEV opening is defined as EEV = EEV + EEV • is the initial EEV opening as a function of the compressor frequency, operation mode, unit model and capacity. • is a correction value for the EEV opening that is based in cooling mode on the relevant indoor unit super heat and compressor temperature.
  • Page 43 CONTROL SYSTEM 11.25 SW Parameters 11.25.1 Indoor Units SW Parameters General Parameters for All Models: Parameters defining the indoor fan speed as a function of Indoor Coil temperature in heat mode (ICT): ICTST Speed ICT to stop indoor fan ICTVLSpeed ICT to go down to very low speed ICTLSpeed ICT to start in very low speed...
  • Page 44 CONTROL SYSTEM 11.25.2 Outdoor Units SW Parameters: Parameter Name DCI25 DCI35 DCI 50 DCI50 DUO Compressor Parameters MinFreqC MaxFreqC MinFreqH MaxFreqH Step1Freq Step2Freq Step3Freq Frequency limits as a function of outdoor air temperature MaxFreqAsOATC MaxFreqAsOAT1H MaxFreqAsOAT2H Compressor Over Heating Protection CTTOH1 CTTOH2 CTTOH3...
  • Page 45: Troubleshooting

    TROUBLESHOOTING TROUBLESHOOTING WARNING!!! When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH VOLTAGE!!! Never open the Outdoor unit before turning off the Power!!! When turned off, the system is still charged (400V)!!! It takes about 3 Min. to discharge the system. Touching the controller before discharging may cause an electrical shock!!! For safe handling of the controller please refer to section 1.6 below.
  • Page 46 TROUBLESHOOTING 1.2 Checking the refrigeration system Checking system pressures and other thermodynamic measures should be done when system is in Test Mode (in Test mode, system operates in fixed settings). The performance curves given in this manual are given for unit performance in test mode when high indoor fan speed is selected. Entering test mode: Set the two indoor units to Cool/16 degrees/High indoor fan speed, or Heat/30 degrees/High indoor fan speed, and enter diagnostics.
  • Page 47 TROUBLESHOOTING 1.3.2 Outdoor unit diagnosis by MSMP and corrective actions Probable Cause Corrective Action Fault Sensors failures of all types Check sensors connections or replace sensors. IPM Fault Electronics HW Check all wiring and jumper problem settings, if OK, replace electronics.
  • Page 48 TROUBLESHOOTING 1.3.3 MSMP Fault Code for Indoor unit: Problem RT-1 is disconnected RT-1 is shorted RT-2 is disconnected RT-2 is shorted RGT is disconnected Reserved Communication mismatch No Communication No Encoder Reserved Outdoor unit fault Reserved Reserved. Reserved Reserved Defrost protection Deicing Protection Outdoor Unit Protection Indoor Coil HP Protection...
  • Page 49 TROUBLESHOOTING 1.3.4 Indoor unit diagnosis by MSMP and corrective actions Probable Cause Corrective Action Fault Sensors failures of all Check sensors connections types or replace sensors. IPM Fault Electronics HW Check all wiring and jumper problem settings, if OK, replace electronics.
  • Page 50 TROUBLESHOOTING 1.5.3 Checking the PCB. Appearance inspect: Check discoloration, nick and connection of copper foil, short-circuit and open circuit, component soldering, bulgy and distortion of electrolytic capacitor. Power circuit check: check voltage of every power level (5V, 12V, 15V) printed on back of PCB. 1.5.4 Checking the Outdoor Fan Motor.
  • Page 51: Exploded Views And Spare Parts Lists

    EXPLODED VIEWS AND SPARE PARTS LISTS EXPLODED VIEWS AND SPARE PARTS LISTS 13.1 Outdoor Unit: DUO 38 DCI / DELTA SM DUO38 1-E.1 GB 13-1 CONTENT...
  • Page 52: Exploded Views And Spare Parts Lists

    EXPLODED VIEWS AND SPARE PARTS LISTS 13.2 Outdoor Unit: DUO 38 DCI / DELTA Part No. Description Front Panel A 433218 Air inlet ring-420 4526340 Axial fan OD=401 4526476 Resin Motor 4526475 Motor Support 433215 Base Painting Assy. 464600021 4526403 Partition Outdoor air thermistor(OAT) 4526774...
  • Page 53: Appendix A

    APPENDIX A APPENDIX A INSTALLATION AND OPERATION MANUAL ► INSTALLATION MANUAL DUO 38 DCI / DELTA 14-1 SM DUO38 1-E.1 GB CONTENT...