JGF Series Indoor Units Outdoor Units ELSI-JGF009-N11 ELAU-VGF009-H11 ELSI-JGF012-N11 ELAU-VGF012-H11 ELSI-JGF018-N11 ELAU-VGF018-H11 ELSI-JGF024-N11 ELAU-VGF024-H11 REFRIGERANT R410A HEAT PUMP SM JGF 1-A.1 GB March- 2011 Version:1...
Page 2
LIST OF EFFECTIVE PAGES LIST OF EFFECTIVE PAGES Note: Changes in the pages are indicated by a “Revision#” in the footer of each effected page (when none indicates no changes in the relevant page). All pages in the following list represent effected/ non effected pages divided by chapters.
JGF//VGF series is monosplit fixed speed air conditioner designed for residential buildings. The IDU JGF is a high-wall mounted type indoor with modern appearance. Following models are included: ELSI-JGF009-N11 / ELAU-VGF009-H11 ELSI-JGF012-N11 / ELAU-VGF012-H11 ELSI-JGF018-N11 / ELAU-VGF018-H11 ELSI-JGF024-N11 / ELAU-VGF024-H11...
INTRODUCTION Indoor Unit The indoor unit is wall mounted, and can be easily fitted to many types of residential locations. It includes: • LED display • Variable speed with PG motor • Motorized flap • High efficiency filtration to ensure a best Air Quality : Advanced filtering combine mechanical, Photo-catalytic + Bi-anti bacterial and observe bad gaseous and smokes.
INTRODUCTION Outdoor Unit The outdoor units can be installed as floor or wall mounted units by using a wall supporting bracket. The metal sheets are protected by anti- corrosion paint work allowing long life resistance. All outdoor units are pre-charged. For further information please refer to the Product Data Sheet, Chapter 2.
Page 7
INTRODUCTION Matching Table INDOOR UNITS OUTDOOR UNITS ELSI-JGF009-N11 ELSI-JGF012-N11 ELSI-JGF018-N11 ELSI-JGF024-N11 √ ELAU-VGF009-H11 √ ELAU-VGF012-H11 √ ELAU-VGF018-H11 √ ELAU-VGF024-H11 SM JGF 1-A.1 GB...
PRODUCT DATASHEET PRODUCT DATA SHEET SHEET JGF009 / VGF009 JGF009 / VGF009 Model Indoor Unit Model Indoor Unit JGF009 JGF009 Model Outdoor Unit VGF009 Installation Method of Pipe Flared Characteristics Units Cooling Heating Capacity (4) 2.64 2.81 Power input (4) 0.82 0.78 EER (Cooling) or COP(Heating) (4)
Page 9
PRODUCT DATASHEET JGF012 / VGF012 JGF012 Model Indoor Unit Model Outdoor Unit VGF012 Installation Method of Pipe Flared Characteristics Units Cooling Heating Capacity (4) 3.22 3.52 Power input (4) 1.00 0.97 EER (Cooling) or COP(Heating) (4) 3.21 3.61 Energy efficiency class 220-240 Power supply Rated current...
Page 10
PRODUCT DATASHEET JGF018 / VGF018 Model Indoor Unit JGF018 Model Outdoor Unit VGF018 Installation Method of Pipe Flared Characteristics Units Cooling Heating Capacity (4) 5.30 5.70 Power input (4) 1.64 1.67 EER (Cooling) or COP(Heating) (4) 3.23 3.41 Energy efficiency class 220-240 Power supply Rated current...
Page 11
PRODUCT DATASHEET JGF024/ VGF024 Model Indoor Unit JGF024 Model Outdoor Unit VGF024 Installation Method of Pipe Flared Characteristics Units Cooling Heating Capacity (4) 6.16 6.50 Power input (4) 1.90 1.90 EER (Cooling) or COP(Heating) (4) 3.24 3.42 Energy efficiency class 220-240 Power supply Rated current...
Page 12
RATING CONDITIONS RATING CONDITIONS TING CONDITIONS Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units). Rating conditions in accordance with ISO 5151 and ISO 13253 (for ducted units). Cooling: Cooling: Indoor: Indoor: C DB 19 C DB 19 C WB C WB Outdoor: 35...
PERFORMANCE DATA & PRESSURE CURVES PERFORMANCE DATA RFORMANCE DATA JGF009 / VGF009 JGF009 / VGF009 5.1.1 5.1.1 Cooling Capacity (kW) Cooling Capacity (kW) Entering Air WB/DB ID Coil( Entering Air WB/DB ID Coil( Entering Air DB Data OD Coil( 15/21 17/24 19/27 21/29...
Page 17
PERFORMANCE DATA & PRESSURE CURVES 5.1.3 Heating Capacity (kW) ENTERING AIR DB ID COIL( ENTERING WB OD COIL( 1.48 0.62 1.42 0.66 1.36 0.70 1.59 0.64 1.53 0.67 1.48 0.71 1.69 0.65 1.63 0.69 1.58 0.72 2.05 0.68 1.97 0.72 1.89 0.76 2.90...
Page 18
PERFORMANCE DATA & PRESSURE CURVES 5.1.4.2 Heating Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB JGF012 / VGF012 5.2.1 Cooling Capacity (kW) Entering Air WB/DB ID Coil( Entering Air DB Data OD Coil( 15/21 17/24 19/27...
Page 19
PERFORMANCE DATA & PRESSURE CURVES LEGEND – Total Cooling Capacity, kW – Sensible Capacity, kW – Power Input, kW WB – Wet Bulb Temp., ( – Dry Bulb Temp., ( – Indoor – Outdoor 5.2.2 Heating Capacity (kW) ENTERING AIR DB ID COIL( ENTERING WB OD COIL( 1.85...
Page 21
PERFORMANCE DATA & PRESSURE CURVES JGF018 / VGF018 5.3.1 Cooling Capacity (kW) Entering Air WB/DB ID Coil( Entering Air Data DB OD Coil( 15/21 17/24 19/27 21/29 23/32 5.40 5.70 5.88 6.02 6.14 3.56 3.75 3.91 4.02 4.10 1.26 1.27 1.27 1.28 1.28...
Page 22
PERFORMANCE DATA & PRESSURE CURVES 5.1.3 Heating Capacity (kW) ENTERING AIR DB ID COIL( ENTERING WB OD COIL( 2.99 1.34 2.88 1.42 2.76 1.49 3.22 1.37 3.11 1.44 2.99 1.52 3.42 1.39 3.31 1.47 3.19 1.55 4.16 1.45 3.99 1.54 3.82 1.64 5.87...
Page 23
PERFORMANCE DATA & PRESSURE CURVES 5.1.6.2 Heating Discharge Pressure VS.Outdoor Temp 25 DB (ºC) 20 DB (ºC) 15 DB (ºC) Outdoor Temp.( WB JGF024 / VGF024 5.4.1 Cooling Capacity (kW) Entering Air WB/DB ID Coil( Entering Air Data DB OD Coil( 15/21 17/24 19/27...
Page 24
PERFORMANCE DATA & PRESSURE CURVES LEGEND – Total Cooling Capacity, kW – Sensible Capacity, kW – Power Input, kW WB – Wet Bulb Temp., ( – Dry Bulb Temp., ( – Indoor – Outdoor 5.4.2 Heating Capacity (kW) ENTERING AIR DB ID COIL( ENTERING WB OD COIL( 3.41...
ELECTRICAL DATA ELECTRICAL DATA MODEL VGF009 VGF012 VGF018 VGF024 To indoor Power Supply 1PH-220-240V-50Hz Max Current, A 5.1A 6.3A 11.1A 11.7 Circuit Breaker, A Power Supply 3x1.0 3x2.5 No. X Cross Section mm Interconnecting Cable 3X1.0+2X0.75 5x2.5 No. X Cross Section mm NOTE Power wiring cord should comply with local laws and electrical regulations requirements.
REFRIGERATION DIAGRAMS REFRIGERATION DIAGRAMS SM JGF 1-A.1 GB...
Page 38
TUBING CONNECTIONS TUBING CONNECTIONS When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at the lowest point of the riser. In case the indoor unit is installed above the outdoor, no trap is required.
CONTROL SYSTEM CONTROL SYSTEM 11.1 Electronic Control 11.1.1 Abbreviations -Alternate Current - Air-Conditioner - ON or OFF status COMP - Compressor - Central Processing Unit E2PROM, EEP - Erase Enable Programmable Read Only Memory - Hardware - Indoor Coil Temperature sensor IF, IFAN - Indoor Fan - Infra Red...
CONTROL SYSTEM 11.1.2 System Operation Concept 11.1.3 Compressor operation For each Mode including POWER OFF & SB, a Min time delay of 3 min before COMP restarting except during outdoor deicing. Whenever COMP starts, it will not stop in 6 min even the RAT is changed. * For the units with memory function, the 1 time of Power ON, there will be no 3 min delay if the previous stage of unit is OFF.
CONTROL SYSTEM 11.1.5.1 OFAN Speed Type The OFAN motor is a one speed AC motor and controlled by the relay on outdoor controller. 11.1.5.2 General rules 1. The OFAN is ON when COMP ON during Cool, Dry and Heat Mode. 2.
CONTROL SYSTEM IFAN speed depends on the indoor coil temperature Anti-cold air function When starting the heating mode, anti-cold air function will be activated and IFAN can run at low speed or stop running. This function will terminate after the unit runs for 2min or the ICT reaches 40 degree.
Page 43
CONTROL SYSTEM off, the air deflector will stay in position 0. The swing is available only when the swing function is set and the indoor fan is running. The louver swing can also be set between L and B, between A and C, between B and D. 11.8 Protections 11.8.1...
Page 44
CONTROL SYSTEM The minimum operating time of heating mode before deicing: a) 40 min after 1 time of power on b) 5 min after system is STBY by RC or temperature condition. 11.8.4.2 Deicing Protection Procedure 1. Start to defrost: COMP stops and starts up 55S later 2....
TROUBLESHOOTING TROUBLESHOOTING 12.1 ELECTRICAL & CONTROL TROUBLESHOOTING 12.1.1 Precautions before Performing Inspection or Repair Be cautious during installation and maintenance. Do operation following the regulations to avoid electric shock and casualty or even death due to drop from high attitude. * Static maintenance is the maintenance during de-energization of the air conditioner.
Page 48
TROUBLESHOOTING 12.1.3 Judgment by Indoor/Outdoor Unit Diagnostics If the malfunction still exists 4min later after stop of unit due to compressor protection, error code will be directly displayed though indoor display. In other situations, error code can be displayed by pressing LIGHT button 6 times within 4s.
EXPLODED VIEW & SPARE PART LIST EXPLODED VIEW & SPARE PART LIST 13.1 Exploded view of indoor unit: JGF009 13-1 SM JGF 1-A.1 GB...
Page 50
EXPLODED VIEW & SPARE PART LIST 13.2 Spare part list of indoor Unit: JGF009 Part Code Part Description 22202135 Rear Case assy 26112201 Motor Press Plate 26152022 Bearing cushion rubber base 10352034 Cross Flow Fan 26112202 Helicoid tongue 10542704 Axile Bush 10582070 Crank 1521210801...
Page 51
EXPLODED VIEW & SPARE PART LIST 13.3 Exploded view of indoor unit: JGF012 13-3 SM JGF 1-A.1 GB...
Page 52
EXPLODED VIEW & SPARE PART LIST 13.4 Spare part list of indoor Unit: JGF012 Part Code Part Description 01252015 Wall-Mounting Frame 2220210101 Rear Case assy 10542704 Axile Bush 10582070 Crank 10352018 Cross Flow Fan 76512051 O-Gasket sub-assy of Bearing 76512203 O-Gasket of Cross Fan Bearing 26152022 Bearing cushion rubber base...
Page 53
EXPLODED VIEW & SPARE PART LIST 13.5 Exploded view of indoor unit: JGF018 13-5 SM JGF 1-A.1 GB...
Page 54
EXPLODED VIEW & SPARE PART LIST 13.6 Spare part list of indoor Unit: JGF018 Part Code Part Description 2001246601_K47371 Front Panel Assy 1112208901 Filter Sub-assy 20012766 Front Case Sub-Assy 24252016 Screw Cover 30565127 Display Board 76712012 Water Tray Glue Plug 01002590 Evaporator Assy 10352019...
Page 55
EXPLODED VIEW & SPARE PART LIST 13.7 Exploded view of indoor unit: JGF024 13-7 SM JGF 1-A.1 GB...
Page 56
EXPLODED VIEW & SPARE PART LIST 13.8 Spare part list of indoor Unit: JGF024 Part Code Part Description 2001246601_K47371 Front Panel Assy 1112208901 Filter Sub-assy 12312214 Rear Case assy 24252016 Screw Cover 30565127 Display Board 01002590 Evaporator Assy 10352019 Cross Flow Fan 26152022 Bearing cushion rubber base 20012766...
Page 57
EXPLODED VIEW & SPARE PART LIST Exploded view of outdoor unit: VGF009,VGF012 13-9 SM JGF 1-A.1 GB...
Page 58
EXPLODED VIEW & SPARE PART LIST 13.9 Spare part list of outdoor Unit: VGF009 Part Code Part Description 22413007 Grille 01533029P Front panel 26233100 Small Handle 01203799P Chassis Sub-assy 01233066 Isolation Sheet 10333427 Axial Flow Fan 150130671 Fan Motor 0111347201 Condenser Assy 01703052 Motor Support Assy...
Page 59
EXPLODED VIEW & SPARE PART LIST 13.10 Spare part list of outdoor Unit: VGF012 Part Code Part Description 22413007 Grille 01533029P Front panel 26233100 Small Handle 01203767P Chassis Sub-assy 01233066 Isolation Sheet 10333427 Axial Flow Fan 150130676 Fan Motor 01113449 Condenser Assy 01703052 Motor Support Assy...
Page 60
EXPLODED VIEW & SPARE PART LIST 13.11 Exploded view of outdoor unit: VGF018 13-12 SM JGF 1-A.1 GB...
Page 61
EXPLODED VIEW & SPARE PART LIST 13.12 Spare part list of outdoor Unit: VGF018 Part Code Part Description 26235401 Small Handle 10335257 Axial-flow Fan 15015057 Fan Motor 0170510702 Motor Support Sub-Assy 01113238 Condenser Assy 07130213 Gas Valve Assy 01255001 Top Cover 01475004 Rear grill 06813401...
Page 62
EXPLODED VIEW & SPARE PART LIST 13.13 Exploded view of outdoor unit: VGF024 13-14 SM JGF 1-A.1 GB...
Page 63
EXPLODED VIEW & SPARE PART LIST 13.14 Spare part list of outdoor Unit: VGF024 Part Code Part Description 26235401 Small Handle 10335257 Axial-flow Fan 15015057 Fan Motor 0170305901 Motor Support Sub-Assy 01113396 Condenser Assy 01255001 Top Cover 0147500401 Rear Grill 02603219 Electric Box Assy 33000039...