Block diagram of the control

4.3 Block diagram of the control

4.3.1

Block diagram of the tension control

Winding diameter
calculation
Line speed
Pr. 720, Pr. 721,
Pr. 773, Pr. 774
Pr. 787, Pr. 788,
Torque command

4.4 Dedicated I/O signal

4.4.1

Input signal list

Use contact input signals by assigning them to Pr. 178 to Pr. 189 (input terminal function selection).
Pr.178 to
Type
Pr.189
setting
Inertia compensation
57
acceleration
Inertia compensation
58
deceleration
Inertia compensation
second acceleration/
59
deceleration time
selection
Dancer/tension
83
control selection
Winding diameter
91
measurement
92
Stall operation
4.4.2

Output signal list

Use output signals by assigning them to Pr. 190 to Pr. 196 (output terminal function selection).
Pr. 190 to Pr. 196
setting
Positive
Negative
logic
logic
Winding diameter
calculation
51
151
completion at a start
56
Winding
Inertia compensation
diameter
Pr. 20, Pr. 713 to Pr. 716
Pr. 756 to Pr. 759
Taper setting
Tension control
Pr. 720 to Pr. 721
Pr. 717, Pr. 720
Signal
X57 Compensates the inertia during acceleration.
X58 Compensates the inertia during deceleration.
X59 Switches the inertia compensation acceleration/deceleration time.
Enables/disables the tension control and the winding diameter compensation function.
OFF: Normal operation.
ON: Tension control and winding diameter compensation are valid.
When the X83 signal is not assigned, normal operation is performed.
To use the tension control and the winding diameter compensation
function, make sure to assign this signal.
Turn ON/OFF the X83 in a stop status to switch between the tension control and
normal operation. After turning ON the X83 signal, wait 20ms or longer to input a
X83
start command (STF/STR).
X91 Turn the X91 signal ON to select the winding diameter measurement mode.
X92 Turn the X92 signal ON to bring the motor into the stall status.
Signal
Y51 Output when winding diameter calculation is completed at an operation start.
Mechanical loss
compensation
Pr. 739 to Pr. 749
Pr. 800 = "6,16"
X83-ON
X83-OFF
Pr. 800 = "1,11"
Description
20ms or more
STF
X83
Description
Torque control
IM
Running speed
Encoder
Refer to
page
62
62
62
32, 59
59
65
Refer to
page
60