12.5.7
Base Heater Setting
The base heater will be working only when RV is "ON" according to the following graph:
Base
Heater
OFF
ON
0
When OAT is faulty the base heater will be "ON" continuously in HEAT mode.
12.5.8
Thermodynamic Protections
12.5.8.1
Protection level definition
Five protection levels are defined:
Normal – No protection status is ON.
Stop-Rise (SR) – System is in protection, first level
D1 - System is in protection, second level
D2 - System is in protection third level
Stop-Compressor (SC) – System is in protection fourth level
12.5.8.2
IDU Protection Level
The ODU receives the protection levels from the IDU. The protection levels are weighted
according to the following table:
Protection Level
Normal
Stop-Rise
D1
D2
Stop-Compressor
12.5.8.3
IDU Protections
12.5.8.3.1
Indoor Coil Defrost Protection
ICT
ICT < -2
-2 ≤ ICT < 0
0 ≤ ICT < 2
2 ≤ ICT < 4
4 ≤ ICT < 6
6 ≤ ICT < 8
8 ≤ ICT
Service Manual - WNG 50_60_80 DCI
2
Weight
0
1
2
3
0
Fast
Increasing
Increasing
SC
SC
D1
D1
SR
SR
SR
SR
Norm
Norm
Norm
Norm
Revision Y05-02
CONTENT
OAT
ICT Trend
No change
Decreasing
SC
SC
D2
D2
D1
D2
SR
D1
SR
SR
Norm
SR
Normal
CONTROL SYSTEM
Fast
Decreasing
SC
D2
D2
D2
D1
SR
12-15