CONTROL SYSTEM
The actual OFAN speeds in heat mode are defined according to the following table
Freq
0
15
25
35
45
55
65
75
85
95
12.5.5.2
Behavior when there is a failure in OFAN
Whenever OFAN fault occurs the compressor will be stopped immediately, except during
deicing protection, then the OFAN will be enabled to be started for maximum 5 times. This rule
is enabled each time the ODU switches to heat/cool modes.
12.5.5.3
Protection Behavior.
When the IDU protection the OFAN will reduce OFSpdReducePrtC and OFSpdReducePrtH
RPM for cool and heat respectively.
In cool mode the OFAN will operate according to CTT or HST protection level:
Protection level
SR, D1 or D2
Stop-Compressor
12.5.5.4
OFAN Force On condition
If HST is higher than 70°C or defined as "HST bad", OFAN will remain ON at the last operating
speed for maximum 2 minutes after COMP is OFF.
12.5.5.5
Night mode
Upon receiving night mode, the OFAN will be limited to max NightRPM speed only in Cool. It
will be back to its normal operation when receiving the mode is cleared.
12.5.6
RV State Setting
During heat mode (except during Deicing) RV is ON.
During cool/SB mode RV is OFF.
RV status will be changed only if COMP is OFF for 3 minutes or more.
12-14
Outdoor air temperature (OAT)
-15
-7
0
7
0
0
0
0
850
850
750
750
850
850
750
750
850
850
750
750
850
850
750
750
850
850
750
750
850
850
750
750
850
850
750
750
850
850
750
750
850
850
750
750
OFAN will add 100 RPM to the target speed
continue to operate for maximum 2 minutes at it last speed or until normal level is
achieved.
Revision Y05-02
CONTENT
14
21
24
0
0
0
500
350
300
520
370
320
540
390
340
560
410
360
580
430
380
600
450
400
620
470
420
640
490
440
650
500
450
Action
Service Manual - WNG 50_60_80 DCI

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dci 60

Table of Contents