Jumper Settings - Electra WNG 50 DCI Service Manual

Wng led/lcd dci inverter series
Hide thumbs Also See for WNG 50 DCI:
Table of Contents

Advertisement

CONTROL SYSTEM

11.25 Jumper Settings

Indoor Unit Controller
11.25.1
0 = Open Jumper (disconnect jumper).
1 = Close Jumper (connect jumper).
Self test Jumper – J1
OPERATION
SELF-TEST
NORMAL
Compensation Jumper – J2
Model
Wall Mounted
Floor/Ceiling
Ducted/cassette
Family selection Jumper – J3, J4 and J5
Family
Reserved
Reserved
Reserved
Wall Mounted (WNG/FLO)
Floor/Ceiling (PXD)
Reserved
Ducted (LS)
Cassette (K)
IDU Model
J8
WNG25
WNG35
WNG50
WNG60
WNG80
PXD25
PXD35
PXD50
K25
K35
K50
LS35
For wall mounted units Jumpers j7, j8 can be configured by service. All other jumpers on
the above table are factory default (cannot be changed by service).
For unit types as Cassettes, floor ceiling, and ducted, jumpers are set by a model plug.
11-14
J1
1
0
J2 (Default)
J5
0
0
0
0
1
1
1
1
J7
0
0
0
1
0
0
0
1
0
0
0
0
0
1
1
0
0
0
0
1
1
0
0
1
Revision Y05-02
CONTENT
Compensation
0
Activated
1
Deactivated
1
Activated
J4
J3
0
0
0
1
1
0
1
1
0
0
0
1
1
0
1
1
Jumper Setting
J6
J5
0
0
0
0
1
0
1
0
1
0
0
1
0
1
0
1
0
1
0
1
0
1
0
1
Service Manual - WNG 50_60_80 DCI
J4
J3
1
1
1
1
0
0
0
0
0
1
0
0
0
0
0
0
1
1
1
1
1
1
1
0