Heater Expansion - Schwank UHE Installation And Owner's Manual

High radiant output low intensity tube type infra red heater
Hide thumbs Also See for UHE:
Table of Contents

Advertisement

NOTE: Access to the manifold pressure test port is on the top of the valve. A 3/16" Allen
Wrench is necessary to check this. When checking or setting the manifold pressure, a water
manometer should be used. Gauges which measure in ounces per square inch or pounds
per square inch are not accurate enough to properly measure or set the pressure.
WARNING
THIS HEATER WILL EXPAND IN LENGTH AS IT HEATS UP. It is a normal
condition that during heat-up and cool-down a tube heater will expand and con-
tract. Allowances for heater expansion must be made in the gas connection, vent-
ing and combustion air ducting. Improper installation, alteration, or adjustment
can result in property damage, injury or death.
The Btuh input and the tube length determine the overall expansion that occurs.
A typical infrared tube installation will expand toward both the Burner and the
vent end.
To allow heater expansion the gas supply must be installed using:
In the USA: a stainless steel Flexible Gas Connector certified for use on an
infrared radiant tube heater (ANSI Z21.24 CSA 6.10);
in CANADA: a Type 1 Hose Connector (CAN/CGA 8.1). Also the flue vent,
and combustion air intake (if used) must be installed in such a manner that
the normal expansion of the heater will be accommodated.
IMPORTANT:
See FIG 18 next page: orientation of connection between heater and gas supply.
TABLE 6
Input
Tube
Rating
Length
Btuh
Feet
60,000
20 / 30
90,000
30 / 40
130,000
40 / 50
160,000
50 / 60
200,000
60 / 70
UHE / EIH I&O Manual
IM100205
RD: MAY 2013
RL: 03D
Approx.
USA: Mandatory
Expansion
Flexible Gas Connector
in Length
ID x Length - Part #
1 1/2"
1/2" x 24" - JL-0771-XX
1 3/4"
1/2" x 24" - JL-0771-XX
2"
1/2" x 24" - JL-0771-XX
2 1/2"
3/4" x 36" - JL-0771-YY
3 1/4"
3/4" x 36" - JL-0771-YY
28
See also Section 13
CANADA: Mandatory
Type '1' Gas Hose
Size - Part #
1/2" x 36" - JL-0771-RC
1/2" x 36" - JL-0771-RC
3/4" x 36" - JL-0771-RB
3/4" x 36" - JL-0771-RB
3/4" x 36" - JL-0771-RB

Advertisement

Table of Contents
loading

This manual is also suitable for:

EihUltraschwank uheInfrasave ultimate eih

Table of Contents