Summary Of Status Indications - Ziton ZP2-F Series Operation Manual

Zp2-f series fire alarm control panel
Table of Contents

Advertisement

Condition
Maximum loops exceeded in a
network
Maximum conventional zones
exceeded in a network
Prealarm
Alert
Configuration device connected
Date and time not set
Event log full
In addition to the above, the following system status events are also added to the
event log (but are not included in the control panel current events report).
Table 5: Other system status events added to the event log
Event
General system events
User sessions
Actions
Rules activation
Conditions deactivation
Power supply faults eliminated
[1] A rule consists of one or more states (combined by Boolean operators) that are configured to
trigger specific system actions after a specific confirmation time. Rules are created by your
installation or maintenance contractor using the configuration utility.

Summary of status indications

This section includes a summary of the control panel status indications.
Standby
Standby is indicated as follows:
The Supply LED is steady
If a sounder delay has been enabled the Sounder Delay LED is steady
If a fire routing delay has been enabled the Fire Routing Delay LED is steady
If a fire protection delay has been enabled the Fire Protection Delay LED is
steady
10
Description
The number of loops in a fire network exceeds the
maximum allowed (32)
The number of conventional zones in a fire network
exceeds the maximum allowed (64)
A device (and corresponding zone) is in prealarm
A device is in alarm but the system is waiting for an
additional alarm event to confirm the zone alarm
A control panel configuration session is initiated via an
external device (PC, laptop etc.)
The system started but the date and time are not set
The control panel event log is full
Description
The control panel is reset, the panel is silenced, a new date
and time is set, the system is initiated etc.
The date and time information for activation and termination
of user sessions
An output group is activated or deactivated or a
programmable system command is executed (via the
Configuration Utility)
A rule is activated [1]
A system condition is deactivated
A previously logged power supply fault is resolved
ZP2-F Series Fire Alarm Control Panel Operation Manual