Preventing Motor Stalling During Operation

Stall prevention during operation prevents the motor from stalling by automatically lowering the Inverter's
output frequency when a transient overload occurs while the motor is operating at a constant speed.
Stall prevention during operation is enabled only during V/f control. If the Inverter output current continues to
exceed the setting in constant L3-06 for 100 ms or longer, the motor speed is reduced. Set whether to enable or
disable deceleration time using constant L3-05. Set the deceleration time using C1-02 (Acceleration time 1) or
C1-04 (Acceleration Time 2).
If the Inverter output current reaches the set value in L3-06 - 2% (Inverter Rated Output Current), the motor
will accelerate again at the frequency set or the acceleration time set.
Related Constants
Name
Con-
stant
Display
Number
Stall preven-
0: Disabled (Runs as set. With a
tion selection
heavy load, the motor may stall.)
during run-
1: Deceleration time 1 (the
ning
deceleration time for the stall
L3-05
prevention function is C1-02.)
2: Deceleration time 2 (the
StallP Run
deceleration time for the stall
Sel
prevention function is C1-04.)
Stall preven-
Effective when L3-05 is 1 or 2.
tion level dur-
Set as a percentage of the Inverter
ing running
rated current.
L3-06
Usually setting is not necessary.
StallP Run
The factory setting reduces the set
Level
values when the motor stalls.
Setting
Description
Range
0 to 2
30 to
200
Control Methods
Change
Factory
during
V/f
Setting
Opera-
V/f
with
tion
PG
1
No
A
A
160%
No
A
A
Machine Protection
Open
Open
Flux
Loop
Loop
Vec-
Vector
Vector
tor
1
2
No
No
No
No
No
No
47
6-