Protective Functions

Preventing Motor Stalling During Operation

Stall prevention during operation prevents the motor from stalling by automatically lowering the inverter out-
put frequency when a transient overload occurs while the motor is operating at a constant speed.
Stall prevention during operation can be enabled in V/f control only. If the Inverter output current continues to
exceed the setting in parameter L3-06 for 100 ms or longer, the motor speed is reduced. Enable or disable the
stall prevention using parameter L3-05. Set the according deceleration times using C1-02 (Deceleration time
1) or C1-04 (Deceleration Time 2).
If the Inverter output current reaches the set value in L3-06 – 2%, the motor will accelerate again to the set fre-
quency.
Related Parameters
Parameter
No.
L3-05
L3-06
Precautions
If the motor capacity is smaller than the Inverter capacity or the motor stalls when operating at the factory set-
tings, lower the stall prevention level during operation.
Setting Precautions
Set the parameters as a percentage taking the inverter rated current to be 100%.
Do not increase the stall prevention level unnecessarily. An extremely high setting can reduce the inverter
lifetime. Also do not disable the function.
If the motor stalls with the factory settings check the V/f pattern (E1-
If the stall level has to be increased very much to get the elevator running check the mechanical system or
consider to use a one size bigger inverter.
Motor Torque Detection / Stacked Car Detection
The inverter provides a torque detection function to detect overtorque or undertorque. An alarm signal can be
output to the digital output terminals M1-M2, M3-M4, or M5-M6.
To use the overtorque/undertorque detection function, set B, 17, 18, 19 (overtorque/undertorque detection
NO/NC) in one of the parameter H2-01 to H2-03 (digital output terminals M1 to M6 function selection).
Overtorque/undertorque is detected by:
observing the output current in V/f control (the inverter rated output current is equal to 100%).
observing the torque reference value in Open Loop and Closed Loop Vector control (the motor rated torque
is equal to 100%).
-34
5
Name
Stall prevention selection during running function
selection
Stall prevention level during running
http://nicontrols.com
Control Methods
Change
Factory
during
Setting
V/f
Operation
1
No
A
150%
No
A
) and the motor setup (E2-
Open
Closed
Loop
Loop
Vector
Vector
No
No
No
No
).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents