Panels, Frame Channels, And Doors - Daikin Skyline IM 777-8 Installation And Maintenance Manual

Outdoor air handler
Table of Contents

Advertisement

Figure 11: D-Gasket Placement Detail (Custom Air
Handling Units Only)
Figure 12: Splice Cap and Splice Plate
S l i d e S p l i c e C a p o n
a n d b e n d e n d s d o w n
5 / 1 6 - 1 8 B o l t
5 / 1 6 - 1 8 N u t
IM 777-8 • Skyline Air Handler
Panels, Frame Channels, and
Doors
Panel Removal
To remove a side or top panel, remove the flat head Torx 30
fasteners along the sides of the panel. Lift off the panel after
removing all fasteners.
Frame Channel Removal
Frame channels that run the length of the unit along the top
can be removed to allow access to both the side and top of
the unit. To remove the frame channel, first remove the side
panel(s). Once the side panel is off, remove the flat head Torx
30 fasteners in the corner of the frame channels. Then pull the
frame channel out the side. Remove any panel screws that are
within one inch of the of the frame since they are engaged into
the gasketed flange of the frame
Figure 13: Removing Panel Screws
S p l i c e
P l a t e
Access Doors and Panels
For routine maintenance, access normally is obtained through
access doors or by removing side panels. Removing all flat head
fasteners along the sides of a panel allow it to be removed.
Fan and filter sections are always provided with a service door
on one side of the unit. If requested on order, doors can be
provided on both sides of the unit. Optional service doors are
available for most section types and are provided based on
customer request.
8
M
I
eChanICal
nsTallaTIon
(Figure
13).
Remove any
panel screws that
engage frame
Remove panel
to remove frame
www.DaikinApplied.com