Symptom
Valve closure fail-
To check the LEV on the connection kit, check the indoor unit liquid pipe tempera-
ure (leaky valve)
ture that appears on the operation monitor on the outdoor unit's multi control board
while operating the indoor unit in question in the FAN mode and the other indoor
units in the cooling mode.
Normally, the LEV is fully closed while the unit is in the FAN mode. If the valve is
leaky, liquid pipe thermistor reading will be lower than normal. If it is significantly
lower than the ambient temperature, valve closure failure is suspected. If the
amount of leakage is insignificant, replacement of LEV is unnecessary unless it is
causing a problem.
Misconnections of
Perform a visual check for disconnected connectors.
connectors or con-
Perform a visual check of lead wire color.
tact failure

7.3. Dip switch setting (Factory setting)

1. Function setting
(1) SW1
Switch position
1
2
3
4
5
6
7
8
9
Auto restart after power failure
10
Power start/stop
Factory setting
(2) SW3
Factory setting
26
Checking Criteria
(A)
Thermistor (RT12, RT13)
(A)
LEV
Function
-
-
-
-
-
-
-
-
Enabled
Enabled
Switch setting
ON
-
-
-
-
-
-
-
-
Disabled
Disabled
Remedy
Replace the LEV
if the amount of
leakage is great.
Disconnect the
connectors on
the control board
and perform a
continuity test.
OFF
-
-
-
-
-
-
-
-