Cascade Kits - Buderus Logamax plus GB162 Applications Manual

Gas condensing boiler
Hide thumbs Also See for Logamax plus GB162:
Table of Contents

Advertisement

GB162 Applications Manual

2.3 Cascade Kits

Buderus offers cascade systems in TL and TR configurations for
up to 4 boilers. For cascades of 5 to 16 boilers use single boiler
manifolds.
TL - Inline installation
All boiler assemblies are installed in one line, enabling an
easy-to-monitor installation in a narrow room.
TR - Back-to-back installation
The boiler assemblies are installed back-to-back on both
sides of a free standing frame, to create a compact installation
which ideally suits rooms without available wall space and
ensures the best possible access to all boilers.
The relevant configuration can be selected on the basis of
the performance required (see table 2).
System gross output
Natural
LPG
gas
k.Btu/hr
k.Btu/hr
kW
290
270
80
333
315
100
580
540
160
623
585
180
666
630
200
870
810
240
913
855
260
956
900
280
999
945
300
1,160
1,080
320
1,203
1,125
340
1,246
1,170
360
1,289
1,215
380
1,332
1,260
400
Table 2 Cascade selection
Low loss
TL- confi guration
header
2½"
TL2, TL3
3"
4"
Table 3 Low loss header configuration
Logamax plus GB162 applications manual | 03.2013
Number of
Cascade
boilers
system options
GB162
TL = inline
TR = back-to-
80
back
kW
Single installation
1
Single installation
TL2 or TR2
2
TL2 or TR2
1
TL2 or TR2
TL3 or TR3
3
TL3 or TR3
2
TL3 or TR3
1
TL3 or TR3
TL4 or TR4
4
TL4 or TR4
3
TL4 or TR4
2
TL4 or TR4
1
TL4 or TR4
TR- confi guration
(inline)
(back-to-back)
TR2
TL4
TR3, TR4
5 boilers and more
The Logamax plus GB162 cascade system can be installed
in 2 different configurations (fig. 5).
The gas connection can be made to either side of the
boilers, independent of the supply and return connections.
Fig. 5 Cascade system configuration varieties
100
kW
1
1
2
1
2
3
1
2
3
4
Technical specifi cations are subject to change without prior notice
TR configuration
TL configuration
| 9