GB162 Applications Manual
Heating curve
The AM10 has a built in linear heating curve that sets the supply
water temperature in relation to the outdoor temperature.
Top of heating curve represents the water temperature at 14°F
(-10°C) outdoor temperature. Based on type of heating system
different water temperatures are recommended for bottom of
heating curve. The boiler follows the heating curve in the AM10
up to the maximum supply water temperature set on the boiler
dial which works as a high limit. In addition the warm weather
shut down (WWSD) turns the heating system off when the
temperature outdoors rises above a certain value.
Heating curve chart in Degrees Fahrenheit:
200
194
190
180
170
160
150
140
130
120
110
100
90
80
Heating curve base point
70
WWSD factory default
60
80
70
Fig. 7 Heating curve chart in Degrees Fahrenheit
Outdoor
Temperature
0
14
(°F)
68
70
Logamax plus GB162 applications manual | 03.2013
Radiant Floor
Panel
Radiators
Baseboard
Hydro Air
Cast Iron Radiators
60
50
40
Outdoor Temperature [°F]
Panel
Radiant Floor
Radiators
120
176
120
160
86
100
85
98
Boiler High Limit
Upper Reference point
14
30
20
Cast Iron
Baseboard
Radiators
162
184
150
167
100
100
98
98
Technical specifi cations are subject to change without prior notice
Use high limit to prevent
radiant floor damage
from overheating.
(not in cascades)
10
0
-10
Hydro Air
190
182
150
148
| 11