User Manual
12.8 Configuring multiple DALI devices (consecutively)
There are situations in which multiple devices need to be configured one after
another. The procedure to consecutively configure multiple devices of the SAME TYPE
AND VERSION differs slightly between MultiOne Basic and MultiOne (full version).
12.8.1 MultiOne Basic
1. Connect one device
2. Connect the USB2DALI interface to the USB port (both black and red USB
plugs (USB-A))
3. Connect the device to the mains
4. Start MultiOne
5. If needed, select All in the Application mode selector
6. Click Scan network in the Network panel to start scanning
7. Select FileOpen to open the required feature configuration file
8. Select the Commands tab
9. At Data field, enter 255; click the Short Addr button. (See NOTE!)
This removes the short address; in the network the short address is shown as
'broadcast'
10. Select the Device features tab
11. Click Write on the toolbar
12. Replace device
13. Click Write on the toolbar
14. Replace device
15. Etc.
12.8.2 MultiOne (full version)
1. Connect one device
2. Connect the USB2DALI interface to the USB port (both black and red USB
plugs (USB-A))
3. Connect the device to the mains
4. Start MultiOne
5. If needed, select All in the Application mode selector
6. Click Scan network in the Network panel to start scanning
7. Select FileOpen to open the required feature configuration file
8. Right click the device in the Network panel and select Reset short address
9. Select the Device features tab
10. Click Write on the toolbar
11. Replace device
12. Click Write on the toolbar
© Philips Lighting B.V. 2014