User Manual
12.3.26
Quick Lamp Start
Product group
FLUO
Description
When the Enable check box is selected, the lamp can be switched on immediately
without the necessity for preheating the lamp. The preheat sequence (typically
between 0.6 seconds and 1.0 seconds) will thus be skipped. This is possible because
heating of the electrodes is not turned off.
Usage
Select the Enable check box to use this feature.
12.3.27
Touch and Dim
Product group
FLUO, LED
Description
This feature defines the startup behavior of a touch and dim controlled device after a
power failure during dimming.
Usage
When the Use last known level check box is selected, the device will start up at the
last known dim level that was used during dimming.
If this is not checked the power on level can be configured between 0 and 100% of
the light.
When the Ignore toggle limits check box is selected, the normal toggle limits are
ignored and dimming starts directly.
If this is not checked the normal toggle limits are used.
© Philips Lighting B.V. 2014