Quell Q307 Manual page 6

Photoelectric smoke alarm
Table of Contents

Advertisement

Installation
Locations to Avoid
• Do not install within 0.9 m (3 ft) of the following: The
door to a kitchen, or a bathroom that contains a tub or
shower, forced air supply ducts used for heating or
cooling, ceiling or whole house ventilating fans, or
other high air-flow areas.
• Do not place the alarm where curtains or other objects
will block the sensor. Smoke must be able to reach the
sensor to accurately detect conditions.
• Install at least 30 cm (12 in) away from fluorescent
lights as electronic noise may cause nuisance alarms.
• Keep out of insect infested areas. Avoid excessively
dusty, dirty or greasy areas. Dust particles may cause
nuisance alarms or failure to alarm.
• Extreme temperatures may effect the sensitivity of the
alarm. Do not install in areas where the temperature is
colder than 5°C or hotter than 45°C, such as garages
and unfinished attics.
• Do not install in areas where the relative humidity (RH)
is greater than 85%. Very humid areas, with moisture
or steam, can cause nuisance alarms.
• Avoid placing smoke alarms in kitchen areas. Normal
cooking may cause nuisance alarms. If a kitchen alarm
is desired, it should have an alarm silencer feature or
be a photoelectric type.
• Do not place in the garage. Particles of combustion are
present when you start your automobile.
• Smoke alarms are not to be used with detector guards
unless the combination (alarm and guard) has been
evaluated and found suitable for that purpose.
• In dead air spaces such as the peak of an "A" frame
ceiling. "Dead Air" at the top may prevent smoke from
reaching the alarm in time to provide early warning.
Refer to images 2A and 2B.