Elektronika SCM60ZD-S Manual page 76

Inverter multi-split system room air conditioner
Table of Contents

Advertisement

Outdoor unit e rror
Current safe stop
Is refrigerant charge quantity adequate?
Is outdoor ventilation condition good?
Compressor overheat
Indoor fan motor error
76
Is output voltage applied to all 3
phases of power transistor?
YES
Is compressor wiring connected
securely?
YES
Inspect compressor. (Broken coil
wire)
YES
YES
Inspect compressor.
YES
Defective inverter
Is discharge pipe sensor resistance
value good?
YES
Is sufficient quantity of refrigerant
circulated?
YES
Defective inverter
Is connector connection good?
YES
Is voltage applied to fan motor?
(Between White - Red)
YES
Defective fan motor
NO
Defective inverter
NO
Connect securely.
NO
Discharge refrigerant.
NO
Secure space for suction and blow out.
Connector connection check, resistance
NO
value check, replacement of discharge pipe
sensor
NO
Does trouble persist after
charging gas?
YES
Clogged capillary tube,
etc.
NO
Correct connector
connection.
NO
Defective indoor unit
PCB
[Broken power transistor,
broken compressor wire]
[Overload operation, compressor
lock, overcharge]
[Gas shortage, defective
discharge pipe sensor]
NO
Gas shortage
[Defective fan motor,
defective indoor PCB]