(v) Dew condensation prevention control for the cooling and dehumidifying operation (STM, SRRM type
only)
<I>
(i) Operation condition: During cooling or dehumidifying operation, 20 minutes elapsed after starting (with decision
speed something other than 0 rps), under the following conditions.
1) When the fan speed is set to "AUTO" or "HI", or operation mode is set to "HI POWER"
(ii) Detail of operation: The upper limit of the decision speed is set to the maximum number of revolutions at fan speed
"MED".
(iii)Rest conditions: Any one of the following conditions.
1) Fan speed set to anything other than "AUTO" or "HI", or operation mode set to something other than " HI POWER"
2) 50 minutes elapsed after starting (with decision speed something other than 0 rps)
3) When decision speed is set to 0 rps
<II>
(i) Operation condition: During cooling or dehumidifying operation after starting (with decision speed set to something
other than 0 rps), and all of the following conditions are satisfied.
1) When fan speed set to "AUTO" or "HI", or operation mode to " HI POWER".
2) When the indoor heat exchanger temp.(Th
minutes of operation.
(ii) Detail of operation: The upper limit of the decision speed is set to the maximum number of revolutions at fan speed
"MED".
(iii)Rest conditions: Any one of the following conditions.
1) Fan speed set to anything other than "AUTO" or "HI", or operation mode set to anything other than " HI POWER"
2) 30 minutes elapsed after this command starts
3) Decision speed set to 0 rps
(w) Drain water overflow prevention function (STM, SRRM type only)
(i) Operation condition: Float switch detects drain water for more than 3 seconds.
(ii) Detail of operation: Sets the decision speed to 0 rps, stops the indoor fan motor, and only lets the drain motor run for
5 minutes. After this operation finishes, if the float switch detects drain water, it will display an error and stop operation.
(iii)Rest conditions: After the drain motor run for 5 minutes, the float switch cannot detect water.
(14) Regulation of outdoor air flow
(a)
The fan operates as follows according to the decision speed. (Except during defrost.)
Decision speed
Outdoor fan speed
(b)
If the outdoor unit's fan speed drops, the outdoor fan is run for 2 minutes at that speed.
44
-R
) rises 5˚C or more relative to the lowest temperature within the first 3
I
1
Cooling
Less than 40
40 or more
Low
Medium
Heating
Less than 50
50 or more
Low
Medium