5.5.5 Refrigerant Piping

(1) Limit
The maximum permissible length of the refrigerant pipes for the outdoor units, and the maximum permissible height difference for
the outdoor units are as shown below.
Length for one indoor unit
Total length for all rooms
Lower installation spot of the indoor unit A
Height
Upper installation spot of the indoor unit B
difference
Maximum height difference of the indoor units C
Length of chargeless refrigerant pipe*
* If the total length for all the rooms exceeds the length of chargeless refrigerant pipe, additionally charge with refrigerant accord-
ing the item 4.
¡ The diameter of the refrigerant pipe:
Class of indoor unit (kW)
Diameter of joint pipe
¡ Outdoor unit and the total connectable indoor units (class kW):
Model
SCM60ZD-S
(2) Connection of refrigerant piping
¡ The service valve corresponding to each indoor unit is as illustrated in the right figure.
¡ Regarding the change in the sizes of gas side pipes (usage of the variable joints); if a
5.0 and 6.0 kW class indoor unit (gas side pipe 12.7) is going to be connected to the
service valves (9.52), variable joints available as accessories must be applied to the
gas side service valves.
[Examples of use of variable diameter joints]
Connection of indoor unit of Class 5.0 to A unit.
Liquid side service valve (ø6.35)
Service
valve for room A
Gas side service
valve (ø9.52)
Copper packing
¡ Securely fit the copper packing between the service valve and the variable diameter joint to prevent shifting.
¡ Cover the pipes with tape so that dust and sand do not enter the pipe until they are connected.
[Connection of pipes]
¡ When connecting the pipes to the outdoor unit, be careful about the discharge of fluorocarbon gas or oil.
¡ Make sure to match the pipes between the indoor unit and the outdoor unit with the correct service valves.
(1) Preparations
Indoor
Push
Remove
¡ Remove the flare nut (from both
liquid and gas sides).
58
A
C
B
2.2 · 2.5 · 2.8 · 3.5kW
Liquid side
Gas side
ø 9.52 · t 0.8
Total of indoor units (class kW)
11.0kW
ø6.35 pipe
5.0 kW class
Indoor unit
ø12.7 pipe
Variable diameter joint (ø9.52-ø12.7)
Outdoor
Push
Remove
¡ Remove the flare nut (from both
liquid and gas sides).
SCM60ZD-S
under 25m
under 40m
under 15m
under 10m
under 25m
30m
5.0 · 60 kW
ø 6.35 · t 0.8
ø 12.7 · t 0.8
A
¡ Fit the removed flare nut to the joint pipe, and then flare it.
ø9.52
Service valve
for room C
ø9.52
Service valve
for room B
ø9.52
Service valve
for room A
Earth screw
Liquid
Gas
Liquid
Gas
side
side
service
service
valve
valve
A dimensions
Liquid side: ø 6.35:9.1dia
Gas side:
ø 9.52: 13.2dia
ø 12.7: 16.6dia