Mitsubishi Electric Mr.SLIM PUHZ-RP1.6VHA Technical & Service Manual page 76

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.SLIM PUHZ-RP1.6VHA:
Table of Contents

Advertisement

11-11. SELECTING FUNCTIONS USING THE REMOTE CONTROLLER
Each function can be set according to necessity using the remote controller. The setting of function for each unit can only be
done by the remote controller. Select function available from the table 1.
<Table 1> Function selections
(1) Functions available when setting the unit number to 00 (Select 00 referring to 4 setting the indoor unit number
on Page 73.)
W1 The functions below are available only when the wired remote controller is used.The functions are not available for floor
standing models.
Function
Power failure
OFF
automatic recovery
ON
Indoor temperature
Operating indoor units
detecting
(The average is considered as indoor temperature.)
Indoor unit with remote controller
Remote controller's internal sensor
LOSSNAY
Not supported
connectivity
Supported (indoor unit not equipped with outdoor air intake)
Supported (indoor unit equipped with outdoor air intake)
Power supply
240V
voltage
220V,230V
Auto energy-saving operation ON
Auto operating
mode
Auto energy-saving operation OFF
2: (Normal)
Frost prevention
3:
temperature
Humidifier control
When the compressor operates, the humidifier also operates.
When the fan operates, the humidifier also operates.
Change of
Standard
For high humidity
defrosting control
(2) Functions available when setting the unit number to 01-03 or AL (07 in case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to 4 setting the
indoor unit number on Page 73.
• When setting functions for a simultaneous- Twin Triple indoor unit system, set the unit number to 01 to 03 for each indoor
unit in case of selecting different functions for each unit referring to 4 setting the indoor unit number on Page 73.
• When setting the same functions for an entire simultaneous Twin Triple-indoor unit system, set refrigerant address to AL
(07 in case of wireless remote controller) referring to 4 setting the indoor unit number on Page 73.
Function
Filter sign
100Hr
2500Hr
No filter sign indicator
Fan speed
standard
High ceiling 1
High ceiling 2
No. of air outlets
4 directions
3 directions
2 directions
Installed options (high-
Not supported
performance filter)
Supported
Horizontal vane
No vanes
setting
Equipped with vane (No.1 setting)
Equipped with vane (No.2 setting)
Energy saving air
Disabled
flow (Heating mode)
Enabled
Direct add-on type
Not supported
humidifier (Only for
Supported
power-cassette)
Swing
Not available
Available
Set temperature in
Available
heating mode 4deg-up
Not available
Fan speed when the
Extra low
heating thermostat is OFF
Low (4-speed model) Low (2-speed model)
Set fan speed
Quiet operation mode of
Normal
power cassette
Quiet
Fan speed when the
Set fan speed
cooling thermostat is OFF
Stop
Detection of abnormality
Available
of the pipe temperature (P8)
Not available
Settings
Settings
Mode
Setting
No.
No.
1
07
2
3
1
08
2
3
1
09
2
3
1
10
2
1
11
2
3
1
12
2
1
13
2
1
23
2
1
24
2
3
1
25
2
1
26
2
1
27
2
1
28
2
76
Initial setting
Mode No. Setting No.
(when sent from the factory)
1
01
2
1
02
2
3
1
03
2
3
1
04
2
1
05
2
1
15
2
1
16
2
1
17
2
Initial setting(when sent from the factory)
Ceiling concealed
Ceiling
Ceiling
4-way Cassette
Concealed
Suspended
PLA-AA
PLA-AA.UK
PEAD-EA
(power-
(power-
PCA-GA
PEAD-GA
cassette)
cassette)
Remarks
The setting is
applied to all
the units in the
same
refrigerant
system.
–: Not available