Mitsubishi Electric Mr.SLIM PUHZ-RP1.6VHA Technical & Service Manual page 31

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.SLIM PUHZ-RP1.6VHA:
Table of Contents

Advertisement

11-3. MALFUNCTION-DIAGNOSIS METHOD BY REMOTE CONTROLLER
11-3-1. Error history of unit
(1) Wired remote controller
Mode number
CENTRALLY CONTROLLED
CHECK
˚C
STAND BY
DEFROST
TEMP.
F
E
G
TIMER SET
PAR-20MAA
C D
1
a)
2
3(1)
c)
Setting number
Refrigerant address
Unit number
1Hr.
ON OFF
˚C
CLOCK
I
FILTER
CHECK MODE
TEST RUN
ERROR CODE
FUNCTION
NOT AVAILABLE
A
ON/OFF
FILTER
J
CHECK TEST
B
H
b)
d)
e)
<In case of trouble during operation>
If there is a trouble on air conditioner, both indoor unit and out-
door unit will stop and digital display shows what was wrong.
1 "CHECK" and refrigerant address are displayed at set tem-
perature display. Error code and unit number are displayed
at clock display alternately.
(If outdoor unit is malfunctioning, unit number is 00.)
2 The refrigerant address and error code initially sent from the
unit are displayed in case of group control system which
one remote controller controls plural refrigerant systems.
3 Press the "ON/OFF" button to cancel error code.
In case of central control by the controller of MELANS, can-
cel the error code by the controller of the MELANS, and in
case of distant-handy combined operation, cancel the error
code by cancelling distant operation.
<Malfunction-diagnosis method at maintenance service>
Digital control has memory function that memorizes latest error
code even if it is cancelled by remote controller or power is
shut off, so error histories can be searched by following the
procedure below.
Search error histories of each unit by remote controller.
1 Turn to self-diagnosis mode.
Press the H "CHECK" button twice within three seconds,
and following display appears.
a) Refrigerant address for self-diagnosis
2 Set refrigerant address number that you want to diagnose.
Press the F
to be diagnosed.
Refrigerant address has number from 00 to 15.
Three seconds after setting, lighted self-diagnosed refriger-
ant address begins blinking and self-diagnosis process
begins.
3 Self-diagnosis result display
(1) When there is an error history.
(Refer to 11-4. for details of error code contents.)
b) Alternating display
c) Error code
d) Attribute of error search
e) Unit number
(2) When there is no error history.
(3) When the address does not exist.
31
(temp.) button to set refrigerant address