Mitsubishi Electric Mr.SLIM PUHZ-RP1.6VHA Technical & Service Manual page 53

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.SLIM PUHZ-RP1.6VHA:
Table of Contents

Advertisement

11-9. TEST POINT DIAGRAM
Outdoor controller circuit board
PUHZ-RP1.6VHA
PUHZ-RP2VHA
PUHZ-RP2.5VHA
PUHZ-RP2.5VHA
1
PUHZ-RP3VHA
PUHZ-RP3VHA
1
Communication
power supply
ZD71 Voltage
developed across:
16-30V DC
+
CNS
(Indoor/outdoor unit
connecting wire)
CN2
Connect to the outdoor
power circuit board (CN2)
1-5:
Power circuit board
Transmitting signal to
the controller circuit board
(0-5V DC)
2-5: Zero cross signal
(0-5V DC)
3-4: Not used
(RP1.6-3VHA)
18V DC (RP4-6VHA)
6-5: 15V DC
7-5: 15V DC
[5: – 1,2,6,7: + ]
[4: – 3: + ]
CNAC
1 to 3: Power supply
for outdoor controller
circuit board
(220V-240V AC)
5 to 7: Power supply
for indoor/outdoor unit
connection wire
(220V-240V AC)
21S4
Four-way valve
63H
High pressure switch
63L
Low pressure switch
Only for RP4-6VHA
52C
52C relay
Only for RP4-6VHA
SV2
RP2.5-3:Bypass valve
RP4-6:Replace valve
Test point for
voltage check
CN4
(Between 1 to 3
Transmission
220-240V AC)
to outdoor
power circuit
board (CN4)
PUHZ-RP4VHA
PUHZ-RP4VHA
1
PUHZ-RP5VHA
PUHZ-RP5VHA
1
PUHZ-RP6VHA
PUHZ-RP6VHA
1
CN52C
52C relay
(
Connect to the
outdoor noise
filter circuit board
(CN52C))
Only for RP1.6-3VHA
FAN11•FAN21
(FAN21 is only for RP4-6VHA.)
Connect to fan motor (MF).
LED1, LED2
Operating inspection
indicators
LED3: Short-circuited
(with jumper wire mounted)
LED4: Not used
(nothing mounted)
53
FAN12
FAN22
(FAN22 is only for RP4-6VHA.)
Connect to fan motor (MF)
(Detection of position)
1 to 5
5V DC pulse
}
2 to 5
(Detected while the
3 to 5
motor is rotating.)
[
]
1 to 4 : +
5 : –
CNDC
300-380V DC
+
}
Connect from
outdoor power
circuit board
(LD1-LD2)
LEV-A, LEV-B
Linear expansion
valve
TH6
Thermistor
<Outdoor 2-phase pipe>
TH7
Thermistor<Outdoor>
TH3
Thermistor
<Outdoor pipe>
TH4
Thermistor
<Discharge>
CNDM
1 to 2: Input of silent mode
1 to 3: Input of external
contact point
CNVMNT
Connected to outdoor
M-NET board
CNM
A-control service
inspection kit
CNMNT
Connected to outdoor
M-NET board
Control power
+
}
supply voltage
5V DC:
4.75-5.25V DC
SW6(J1~J6)
Model select
SW1
Forced defrost,
detect history
record reset,
refrigerant address
SW4
SWP
Test operation
Pump down
SW5
CN31
Function
Emergency
switch
operation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents