(2) Digital wireless remote controller
<In case of trouble during operation>
When a malfunction occurs to air conditioner, both indoor unit and outdoor unit will stop and operation lamp blinks to inform
unusual stop.
<
Malfunction-diagnosis method at maintenance service>
CHECK
CHECK
display
TEMP
ON/OFF
ON/OFF
button
AUTO STOP
FAN
AUTO START
MODE
VANE
CHECK LOUVER
CHECK
TEST RUN
button
RESET
SET
CLOCK
[Procedure]
1. Press the CHECK button twice.
Refrigerant
address
display
2. Press the temperature
Temperature
buttons.
button
3. Point the remote controller at the
HOUR
sensor on the indoor unit and
button
h
press the HOUR button.
min
4. Point the remote controller at the
sensor on the indoor unit and
press the ON/OFF button.
Malfunction diagnosis can be performed only for refrigerant system control-
ling wireless units.
Inspected unit
Error code
Beep output
Operation LED
beep O 1 time
1 sec. O 1 time
P1
beep O 2 times
P2
1 sec.O 2 times
beep O 4 times
P4
1 sec.O 4 times
beep O 5 times
P5
1 sec.O 5 times
beep O 6 times
P6
1 sec.O 6 times
beep O 8 times
P8
1 sec.O 8 times
beep O 2 times
P9
1 sec.O 2 times
E4, E5
Other than above
Other than above
33
• "CHECK" lights, and refrigerant
address "00" flashes.
• Check that the remote controller's
display has stopped before continuing.
• Select the refrigerant address of the
indoor unit for the self-diagnosis.
Note: Set refrigerant address using the
outdoor unit's DIP switch (SW1).
(For more information, see the
outdoor unit installation manual.)
• If an air conditioner error occurs, the
indoor unit's sensor emits an intermit-
tent buzzer sound, the operation light
flashes, and the error code is
output.
(It takes 3 seconds at most for error
code to appear.)
• The check mode is cancelled.
Inspected unit
Check code
Beep output
F1–F9
beep beep O 1 time
U0–UP
E6–EE
Other than above
No check code
No output
(normal)
No check code
(mistake of match-
beep beep beep
ing with refrigerant
address)
Operation LED
(0.4sec+0.4sec)
O 1 time
Other than above
Lights off
Lights off