Technical Data

11 Technical Data
PV generator connection data
Max. input voltage
Input voltage, MPP range
Max. input current
Max. input power
Voltage ripple
Internal consumption during operation
a) The maximum open circuit voltage, which can occur at a cell temperature of -10 °C, must not exceed the maximum input
voltage.
Grid Connection Data
Nominal output power
Max. output power
Nominal output current
Max. output current
Max. fuse protection
Harmonic distortion of output current
(at T
< 2 %, P
> 0.5 P
HD
AC
Nominal AC voltage
Voltage range
(extended operating range)
AC- Grid frequency
Frequency range
(extended operating range)
Power factor (at nominal output power) cos Phi
Overvoltage category
Test voltage (50 Hz)
Test surge voltage
Internal consumption in night mode
36
SB3300TLHC-IEN094121
U
DC max
Upv
I
PV max
P
DC
U
pp
P
ACnom
P
ACmax
I
ACnom
I
AC max
K
IAC
)
ACNom
U
ACnom
U
AC
f
ACnom
f
AC
SMA Solar Technology AG
Setting
a)
750 V
125 V ... 600 V
11 A
3440 W
< 10 % of the input voltage
< 10 W (standby)
Setting
3000 W
3300 W
13 A
16 A
32 A
< 4 %
220 V / 230 V / 240 V
180 ... 260 V AC
50 Hz
45.5 ... 52.5 Hz
1
III
1.65 kV
4 kV (serial interface: 6 kV)
0.25 W