4 Mounting
4.1 Selecting the Mounting Location
DANGER!
Danger to life due to fire or explosion!
Despite careful construction, a fire can occur with electrical devices.
• Do not mount the Sunny Boy on flammable construction materials.
• Do not mount the Sunny Boy near highly flammable materials.
• Do not install the Sunny Boy in potentially explosive areas!
CAUTION!
Danger of burn injuries due to hot housing parts!
The temperature of individual parts of the housing, in particular the temperature of the
heatsink and the components inside the Sunny Boy can reach more than 60 °C. Touching
could result in burns!
Weight
CAUTION!
Risk of injury due to the heavy weight of the Sunny Boy!
The Sunny Boy weighs more than 28 kg.
• Consider the weight of the Sunny Boy when choosing the location and method of
installation.
Ambient Conditions
• The mounting location and mounting method must be suitable for the weight and dimensions.
• Mount on a solid surface.
• The installation location must be accessible at all times (do not mount in inaccessible places).
• The Sunny Boy must be easy to remove from the mounting location at any time.
• The Sunny Boy must not be in operation in ambient temperatures outside the range of -25 °C
and +60 °C. For optimal operation, the ambient temperature should not exceed +40 °C.
• Do not expose the Sunny Boy to direct sunlight, so as to avoid power reduction due to excessive
heating.
10