Advertisement

5. Attach one end of the 50' x 3/16" O.D. factory provided pneumatic tubing to the sensor's top port,

Units with Statitrac™

1. Open the filter access door, and locate the Statitrac Transducer Assembly illustrated in
2. Route the opposite end of the tubing to a suitable location inside the building. This location
Figure 15. Pressure Tubing
RT-SVX34C-EN
and the other end of the tubing to the connector in the vertical support. Discard any excess
tubing.
Figure 16, p.
28. There are two tube connectors mounted on the left of the solenoid and
transducers. Connect one end of the field provided 1/4" (length 50-100 ft.) or 3/8" (length greater
than 100 ft.) O.D. pneumatic tubing for the space pressurization control to the fitting indicated
in the illustration.
should be the largest open area that will not be affected by sudden static pressure changes.
Installation General Requirements