Installation Electrical
Figure 32. Space Temperature Averaging
Table 15. Temperature vs. Resistance (temperature vs. resistance coefficient is negative)
Degrees F°
48
Nominal
Resistance
-20°
170.1 K - Ohms
-15°
143.5 K - Ohms
-10°
121.4 K - Ohms
-5°
103.0 K - Ohms
87.56 K - Ohms
74.65 K - Ohms
10°
63.80 K - Ohms
15°
54.66 K - Ohms
20°
46.94 K - Ohms
25°
40.40 K - Ohms
30°
34.85 K - Ohms
35°
30.18 K - Ohms
40°
26.22 K - Ohms
45°
22.85 K - Ohms
To RTRM J6-1 and J6-2
or to ZSM terminals 1 and 2
or NSB panel terminals S1
and S2. Shield to terminal 11.