Table 7.
27½-50 Ton Electrical Service Sizing
Allowable
Electrical
Model
Characteristics
208/60/3
230/60/3
TC/TE/
YC*600
460/60/3
575/60/3
Notes:
1. All customer wiring and devices must be installed in accordance with local and national electrical codes.
2. 100% Power Exhaust is with or without Statitrac™.
Table 8.
Nominal
Unit Size
RT-SVX34C-EN
Data—60Hz1
Compressor
Voltage
RLA
Range
No/Ton
(Ea.)
2/13,1/
187-229
50.5/56.0 315/351
15
2/13,1/
207-253
50.5/56.0 315/351
15
2/13,1/
414-506
23.0/27.5 158/197
15
2/13,1/
517-633
19.0/23.0 136/146
15
Electrical Service Sizing Data — Crankcase Heaters — (Heating Mode Only)—60Hz
(Tons)
200
27½ - 35
1
40, 50
2
Fan Motors
Supply
LRA
(Ea.)
HP
FLA
10.0
29.0
15.0
40.7
20.0
56.1
10.0
25.2
15.0
37.8
20.0
49.4
10.0
12.6
15.0
18.9
20.0
24.7
10.0
10.1
15.0
15.1
20.0
19.6
FLA Add
Unit Voltage
230
460
575
1
1
2
1
Installation Electrical
Condenser
FLA
100%
No HP
(Ea.) 50%
No.
4
1.1
7.0
1
4
1.1
7.0
1
4
1.1
3.5
1
4
1.1
2.8
1
1
1
Exhaust
FLA
2
HP
(Ea.)
2
1.5
5.4
2
1.5
5.4
2
1.5
2.7
2
1.5
2.2
33